TABLE 3: 

Diagnostic Label

Status LED

Status LED Description

Status LED Troubleshooting Information

Green “POWER”

Module has power

Supply voltage is present at module terminals

Red “TRIP”

Thermostat demand signal Y1 is present, 
but the compressor is not running

1. Compressor protector is open

2. Outdoor unit power disconnect is open

3. Compressor circuit breaker or fuse(s) is open

4. Broken wire or connector is not making contact

5. Low pressure switch is open

6. Compressor contactor has failed open

Yellow “ALERT”
Flash Code 2

System Pressure Trip
Low pressure switch fault

1. Low refrigerant charge

2. Evaportor blower is not running

3. Evaportor coil is frozen 

4. Faulty metering device

5. Condenser coil is dirty

6. Liquid line restriction (filter drier blocked if present in system)

Yellow “ALERT”
Flash Code 3

Short Cycling
Compressor is running only briefly

1. High pressure switch fault

2. Condenser coil poor air circulation (dirty, blocked, damaged)

3. Condenser fan is not running

4. Return air duct has substantial leakage

5. Thermstat demand signal is intermittent

Yellow “ALERT”
Flash Code 4

Locked Rotor

1. Run capacitor has failed 

2. Low line voltage (contact utility if voltage at disconnect is low)

3. Excessive liquid refrigerant in compressor

4. Compressor bearings are seized

Yellow “ALERT”
Flash Code 5

Open Circuit

1. Outdoor unit power disconnect is open

2. Compressor circuit breaker or fuse(s) is open

3. Compressor contactor has failed open

4. Low pressure switch is open

5. Open circuit in compressor supply wiring or connections 

6. Unusually long compressor protector reset time due to exteme ambient 

termperature

7. Compressor windings are damaged

Yellow “ALERT”
Flash Code 6

Open Start Circuit
Current only in run circuit

1. Run capacitor has failed

2. Open circuit in compressor start wiring or connections

3. Compressor start winding is damaged

Yellow “ALERT”
Flash Code 7

Open Run Circuit
Current only in start circuit 

1. Open circuit in compressor run wiring or connections

2. Compressor run winding is damaged

Yellow “ALERT”
Flash Code 8

Welded Contactor
Compressor always runs

1. Compressor contactor has failed closed

2. Thermostat demand signal not connected to module

Yellow “ALERT”
Flash Code 9

Low Voltage
Control circuit < 17 VAC

1. Control circuit transformer is overloaded

2. Low line voltage (contact utility if voltage at disconnect is low)

Summary of Contents for CZE03811 Series

Page 1: ...hazardous situation which if not avoided may result in minor or moderate injury It is also used to alert against unsafe practices and hazards involving only property dam age INSPECTION As soon as a un...

Page 2: ...coil face to coil face If the unit is to be installed on a hot sun exposed roof or a black topped ground area the unit should be raised sufficiently above the roof or ground to avoid taking the accum...

Page 3: ...care must be taken to avoid sharp bends which may cause a restriction 2 The lines should be installed so that they will not obstruct service access to the coil air handling system or filter 3 Care mus...

Page 4: ...wrench back out counter clockwise until valve stem just touches the chamfered retaining wall See Page 4 PRECAU TIONS DURING BRAZING SERVICE VALVE 13 Replace plunger cap finger tight then tighten an ad...

Page 5: ...ply connections FIELD CONNECTIONS CONTROL WIRING 1 Route low voltage wiring into bottom of control box Make low volt age wiring connections inside the junction box per Figures 7 9 2 The complete conne...

Page 6: ...oil match up Some indoor coil matches may require additional charge See tabular data sheet provided in unit literature packet for charge requirements The TOTAL SYSTEM CHARGE must be permanently stampe...

Page 7: ...Owner Assist owner with processing warranty cards and or online registration Review Owners Manual provide a copy to the owner and provide guid ance on proper operation and maintenance Instruct the ow...

Page 8: ...ort AlertTM module marked R C and S 24 VAC Power Wiring The Comfort AlertTM module requires a con stant nominal 24 VAC power supply The wiring to the module s R and C terminals must be directly from t...

Page 9: ...ermittent Yellow ALERT Flash Code 4 Locked Rotor 1 Run capacitor has failed 2 Low line voltage contact utility if voltage at disconnect is low 3 Excessive liquid refrigerant in compressor 4 Compressor...

Page 10: ...103142 YIM A 1204 10 Unitary Products Group SECTION IX WIRING DIAGRAM FIGURE 10 Wiring Diagram...

Page 11: ...103142 YIM A 1204 Unitary Products Group 11 NOTES...

Page 12: ...ubject to change without notice Printed in U S A 103142 YIM A 1204 Copyright by York International Corp 2004 All rights reserved Supersedes Nothing Unitary 5005 Norman Product York OK Group Drive 7306...

Reviews: