360101-XTG-A-0108
Johnson Controls Unitary Products
5
SEER = Seasonal Energy Efficiency Ratio - the total cooling output in BTU's during a normal annual usage period for cooling divided by the
total electric power input in watt-hours during the same period.
TABLE 1: PHYSICAL DATA
MODELS
DEB
018
024
030
036
042
048
060
EVAPORATOR
BLOWER
CENTRIFUGAL BLOWER (Dia. x Wd. in.)
9 X 6
10 X 8
10 X 8
10 x 8
11 X 10
11 x 10
11 x 10
FAN MOTOR HP
½
½
½
1
EVAPORATOR
COIL
ROWS DEEP
2
2
2
2
2
2
3
FINS PER INCH
13
15
15
15
15
13
16
FACE AREA (Sq. Ft.)
2.19
2.81
4.38
4.38
4.38
5.62
5.26
CONDENSER
FAN
PROPELLER DIA. (in.)
22
22
22
22
22
22
22
FAN MOTOR HP
1/4
1/4
1/4
1/4
1/4
1/4
1/4
NOM. CFM TOTAL
1,800
2,200
2,400
2,400
2,400
2,800
2,800
CONDENSER
COIL
ROWS DEEP
1
1
1
1
1
1
1
FINS PER INCH
18
16
20
18
16
13
20
FACE AREA (Sq. Ft.)
8.3
8.3
8.3
8.3
11.7
16.4
16.4
CHARGE
REFRIGERANT 22 (lbs./oz.)
3 / 4
3 / 5
3 / 13
3 / 10
4 / 8
5 / 15
5 /15
FILTER
FACE AREA (Sq. Ft.) / Qty. / Size
2.14 / 2 / 14" x 22"
COMPRESSOR HERMETIC, QTY. = 1 (Type)
Recip.
Recip.
Recip.
Recip.
Recip.
Scroll
Scroll
3
4
3
4
3
4
TABLE 2: RATINGS - ARI
Model DEB
Cooling Capacity
1
80/67-95 °F
Sound Rating
2
(decibels)
Electric Heat
Nom. Capacity
KW
(single phase)
MBH
EER
018
17.6
8.8
76
5.0, 7.5
024
23.0
9.1
76
5.0. 7.5. 10.0
030
29.0
8.9
79
5.0, 7.5, 10.0, 15.0
036
35.2
8.7
81
5.0, 7.5, 10.0, 15.0
042
40.5
9.4
83
5.0, 7.5, 10.0, 15.0
048
46.5
8.8
81
10.0, 15.0, 20.0, 25.0
060
59.0
8.8
79
10.0, 15.0, 20.0, 25.0
1. Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.