360101-XTG-A-0108

14

Johnson Controls Unitary Products

*

 KW listed is for 240 volts, use table at top of page for 208 or 230 volts.

TABLE 12: ELECTRICAL DATA (BASIC UNIT)

Model

DEB

Volt

Voltage

Limitations

1

1. Rated in accordance with ARI Standard 110, utilization range “A”.

Compressors

Cond. 

Fan

Motors

Supply Air

Blower

Motor

MCA

(Amps)

Max

Fuse

Size

2

(Amps)

2. Dual element, time delay type

Max HACR/

Breaker

 Size

(Amps)

Unit

Power

Factory

Transformer

Size
(VA)

Min.

Max.

RLA

LRA

FLA

FLA

018

208/230-1-60

187

253

9.0

48.0

1.1

2.6

14.9

20

20

.96

40

024

208/230-1-60

187

253

11.5

60.0

1.1

2.6

18.1

25

25

.96

40

030

208/230-1-60

187

253

14.7

73.0

1.1

2.6

22.1

30

30

.96

40

036

208/230-1-60

187

253

17.3

94.0

1.1

3.5

26.2

35

35

.96

40

042

208/230-1-60

187

253

15.5

86.0

1.1

3.5

23.9

30

30

.96

40

048

208/230-1-60

187

253

24.4

140.0

1.3

4.0

35.8

45

45

.96

40

060

208/230-1-60

187

253

28.9

165.0

1.3

4.0

44.4

60

60

.96

40

ELECTRIC HEAT

CORRECTION

FACTORS

NOMINAL VOLTAGE

VOLTAGE

KW CAP.

MULTIPLIER

240

208

.75

230

.92

TABLE 13: ELECTRICAL DATA (COOLING/ELECTRIC HEAT)

Model

DEB

Power

Supply

Compressor

Cond..

Fan

Motor

FLA

Supply

Air Blower

Motor

FLA

ELECTRIC HEAT ACCESSORY

Min.

Circuit

 Ampacity

(Amps)

Max.

Fuse

SizE

1

(Amps)

1. Dual element, time delay type.

Max.

HACR

2

Breaker

Size

(Amps)

2. Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.

RLA

LRA

Model No.

Stage

KW

Total

AMPS

018

208/230-1-60

9.0

48.0

1.1

2.6

2NH04500506

1

3.8/5.0*

18.1/20.8

25.8/29.3

30/30

30/30

2NH04500706

2

5.6/7.5*

27.1/31.3

37.1/42.3

40/45

40/45

024

208/230-1-60 11.2

60.0

1.1

2.6

2NH04500506

1

3.8/5.0*

18.1/20.8

25.8/29.3

30/30

30/30

2NH04500706

2

5.6/7.5*

27.1/31.3

37.1/42.3

40/45

40/45

2NH04501006

2

7.5/10.0* 36.1/41.7

48.4/55.3

50/60

50/60

030

208/230-1-60 12.0

73.0

1.1

2.6

2NH04500506

1

3.8/5.0*

18.1/20.8

25.8/29.3

30/30

30/30

2NH04500706

2

5.6/7.5*

27.3/31.3

37.1/42.3

40/45

40/45

2NH04501006

2

7.5/10.0* 36.1/41.7

48.4/55.3

50/60

50/60

2NH04501506

2

11.3/15.0* 54.2/62.5

71.0/81.4

80/90

80/90

036

208/230-1-60 17.3

94.0

1.1

3.5

2NH04501006

2

7.5/10.0* 36.1/41.7

49.5/56.5

50/60

50/60

2NH04501506

2

11.3/15.0* 54.2/62.5

72.1/82.5

80/90

80/90

042

208/230-1-60 15.5

86.0

1.1

3.5

2NH04500506

1

3.8/5.0*

18.1/20.8

26.9/30.4

35/35

35/35

2NH04500706

2

5.6/7.5*

27.1/31.3

38.2/43.4

40/45

40/45

2NH04501006

2

7.5/10.0* 36.1/41.7

49.5/56.5

50/60

50/60

2NH04501506

2

11.3/15.0* 54.2/62.5

72.1/82.5

80/90

80/90

048

208/230-1-60 24.4

140.0

1.3

4.0

2NH04501006

2

7.5/10.0* 36.1/41.7

50.1/57.1

60/60

60/60

2NH04501506

2

11.3/15.0* 54.2/62.5

72.1/83.1

80/90

80/90

2NH04502006

2

15.0/20.0* 72.2/83.3

95.3/109.2 100/110 100/110

2NH04502506

2

18.8/25.0* 90.3/104.2 117.8/135.2 125/150 125/150

060

208/230-1-60 28.9

165.0

1.3

7.0

2NH04501006

2

7.5/10.0* 36.1/41.7

53.9/60.8

70/70

70/70

2NH04501506

2

11.3/15.0* 54.2/62.5

76.5/86.9

80/90

80/90

2NH04502006

2

15.0/20.0* 72.2/83.3

99.0/112.9 100/125 100/125

2NH04502506

2

18.8/25.0* 90.3/104.2 121.6/139.0 125/150 125/150

Summary of Contents for AFFINITY 360101-XTG-A-0108

Page 1: ...needs to carry less inventory LOWER INSTALLATION COST Installation time and costs are reduced by easy power and control wiring connections The small base dimension means less space is required on the...

Page 2: ...2 TON DEB018 6 4 COOLING CAPACITIES 2 TON DEB024 7 5 COOLING CAPACITIES 2 1 2 TON DEB030 8 6 COOLING CAPACITIES 3 TON DEB036 9 7 COOLING CAPACITIES 3 1 2 TON DEB042 10 8 COOLING CAPACITIES 4 TON DEB0...

Page 3: ...condenser fan does not disrupt neighboring areas and does not dry out vegetation surrounding the unit The warm air from the top mounted fan is blown up away from the structure and any landscaping Thi...

Page 4: ...ed side return and unit mounted down shot return applications Damper capable of providing 0 thru 50 of outdoor air field supplied Closes on power loss includes hood and screen assembly RECTANGLE TO RO...

Page 5: ...0 2 400 2 400 2 400 2 800 2 800 CONDENSER COIL ROWS DEEP 1 1 1 1 1 1 1 FINS PER INCH 18 16 20 18 16 13 20 FACE AREA Sq Ft 8 3 8 3 8 3 8 3 11 7 16 4 16 4 CHARGE REFRIGERANT 22 lbs oz 3 4 3 5 3 13 3 10...

Page 6: ...6 17 2 16 5 14 4 14 9 Total Power Input kW 1 99 2 00 1 96 1 94 2 05 2 06 2 02 2 00 2 11 2 12 2 08 2 06 2 14 2 15 2 10 2 09 2 16 2 17 2 13 2 11 Sensible Capacity MBH 1 Entering Dry Bulb F 86 8 7 12 0 1...

Page 7: ...9 7 19 7 Total Power Input kW 2 61 2 58 2 55 2 51 2 67 2 64 2 60 2 56 2 72 2 69 2 65 2 62 2 87 2 84 2 79 2 76 3 01 2 98 2 93 2 90 Sensible Capacity MBH 1 Entering Dry Bulb F 86 13 4 16 7 17 9 17 9 14...

Page 8: ...Power Input kW 3 38 3 28 3 22 3 22 3 45 3 35 3 29 3 28 3 52 3 42 3 36 3 35 3 66 3 55 3 49 3 48 3 79 3 68 3 62 3 61 Sensible Capacity MBH 1 Entering Dry Bulb F 86 16 5 21 3 22 2 22 3 18 5 23 4 23 1 23...

Page 9: ...ut kW 4 05 3 92 3 93 3 85 4 07 3 94 3 95 3 87 4 09 3 96 3 97 3 89 4 15 4 02 4 02 3 95 4 21 4 08 4 08 4 00 Sensible Capacity MBH 1 Entering Dry Bulb F 86 17 5 23 3 25 0 24 4 19 9 26 3 26 6 26 0 22 3 29...

Page 10: ...20 4 22 4 47 4 35 4 27 4 29 4 54 4 42 4 34 4 35 4 69 4 57 4 48 4 50 4 84 4 71 4 63 4 64 Sensible Capacity MBH 1 Entering Dry Bulb F 86 22 4 29 3 30 8 31 2 24 8 32 1 32 0 32 4 27 3 34 9 33 1 33 6 29 3...

Page 11: ...21 5 21 5 49 5 43 5 34 5 33 5 62 5 55 5 46 5 45 5 72 5 66 5 56 5 55 5 83 5 76 5 66 5 65 Sensible Capacity MBH 1 Entering Dry Bulb F 86 27 0 33 2 37 8 37 4 29 6 36 1 38 3 37 9 32 3 39 1 38 8 38 3 34 3...

Page 12: ...58 7 07 6 90 6 79 6 75 7 25 7 06 6 96 6 91 7 47 7 28 7 17 7 12 7 69 7 50 7 38 7 33 Sensible Capacity MBH 1 Entering Dry Bulb F 86 33 5 42 4 45 0 45 3 37 5 47 1 46 9 47 2 41 4 51 8 48 8 49 1 44 9 53 7...

Page 13: ...1205 576 1094 547 Medium 1674 614 1590 590 1506 567 1400 535 1295 502 1190 470 1063 428 Low 1579 567 1512 546 1444 525 1377 504 1282 476 1188 447 1093 418 048 4 0 High 1985 870 1939 850 1897 830 1813...

Page 14: ...Model No Stage KW Total AMPS 018 208 230 1 60 9 0 48 0 1 1 2 6 2NH04500506 1 3 8 5 0 18 1 20 8 25 8 29 3 30 30 30 30 2NH04500706 2 5 6 7 5 27 1 31 3 37 1 42 3 40 45 40 45 024 208 230 1 60 11 2 60 0 1...

Page 15: ...hange without notice Certified dimensions will be provided upon request UNIT CONDENSATE CONNECTION NPTI TRAP REQUIRED OVERALL SIDE SUPPLY AIR OPENING SIDE RETURN AIR OPENING COMPRESSOR SERVICE ACCESS...

Page 16: ...Shipping Weight Operating Weight Corner Weights Economizer lbs Roof Curb lbs A B C D 018 318 313 86 76 73 83 40 8 70 14 75 024 324 319 88 77 75 85 030 333 328 85 81 82 86 036 338 333 91 80 78 88 042...

Page 17: ...OWER SUPPLY SUPPLY AIR DUCT RETURN AIR DUCT FIELD SUPPLIED DISCONNECT SWITCH LOCATED TO REAR OF UNIT CONTROL WIRING TO INDOOR THERMOSTAT SLAB ON GROUND INSTALLATION ROOF CURB INSTALLATION BOTTOM DUCT...

Page 18: ...ED PANELS 22 14 OPENING FOR RETURN AIR DUCT OPENING FOR SUPPLY AIR DUCT RECOMMENDED DUCT SIZE SUPPLY AIR DUCT x RETURN AIR DUCT x UNIT BASE RAIL UNIT BASE WOOD NAILER 8 MIN ABOVE FINISHED ROOF CURB FR...

Page 19: ...trols Unitary Products 19 FIGURE 9 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY DEB MODELS 15695BASH0301 SEE DETAIL A T2 M1 2 DETAIL A BLK BLK CCH L1 T1 OPTIONAL CCH S P CONFIGURATION BLK BLK CCH...

Page 20: ...tandard 24 O C beams without modification to building structure duct work and base unit 10 Condensate pan shall be internally sloped and conform to ASHRAE 62 89 self draining standards with 3 4 NPTI c...

Page 21: ...section shall have a primary limit control s and automatic reset to prevent the heating element system from operating at an excessive temperature 3 The heating section assembly shall slide out of the...

Page 22: ...360101 XTG A 0108 22 Johnson Controls Unitary Products...

Page 23: ...360101 XTG A 0108 Johnson Controls Unitary Products 23...

Page 24: ...hout notice Printed in U S A 360101 XTG A 0108 Copyright 2008 by Johnson Controls Inc All rights reserved Supersedes 263146 XTG A 0206 036 21753 001 A 0206 Johnson Controls Unitary Products 5005 York...

Reviews: