MECHANICAL SPECIFICATIONS

GENERAL DESCRIPTION

Units shall be factory-assembled, single packaged, Electric 
Cooling units, designed for outdoor mounted installation. They 
shall have built in, equal size, field convertible duct connections 
for down discharge supply/return or horizontal discharge 
supply/return.

The units shall be factory wired, piped, charged with R-22 
refrigerant and factory tested prior to shipment. All unit wiring 
shall be both numbered and color coded.

All units shall be manufactured in a facility certified to ISO 9001 
standards, and the cooling performance shall be tested in 
accordance with ARI test procedures. Units shall be certified to 
UL 1995/CAN/CSA C22.2 No. 236 standards.

UNIT CABINET

1.

Unit cabinet shall be constructed of a combination of G60 
and G90 galvanized steel, with exterior surfaces coated 
with a non-chalking, powdered paint finish, certified at 
750 hours salt spray test per ASTMB117 standards.

2.

The unit top shall be a single piece “Water Shed” design, 
with drip edges and no-seam corners to provide optimum 
water integrity

3.

Unit shall have a rigidly mounted condenser coil guard to 
provide protection from objects and personnel after 
installation.

4.

Indoor blower section shall be insulated with up to 3/4”  
thick, aluminum, foil faced insulation, fastened to prevent 
insulation from entering the air stream.

5.

Cabinet panels shall be “large” size, easily removable for 
servicing and maintenance, with built-in lift handles.

6.

Unit shall be built on a formed, “Super-Structure” design 
base pan, with embossments at critical points to add 
strength, rigidity and aid in minimizing sound.

7.

Full perimeter base rails shall be provided to assure 
reliable transit of equipment, overhead rigging, fork truck 
access and proper sealing on roof curb applications. Base 
rails shall be removable, when required, to lower unit 
height.

8.

Filters shall be furnished and be accessible through a 
removable access door, sealed air tight. (Single phase 
models - accessory kit available. Three phase models - 
standard from factory.)

9.

Units vertical discharge and return duct configuration shall 
be designed to fit between standard 24” O.C. beams 
without modification to building structure, duct work and 
base unit.

10. Condensate pan shall be internally sloped and conform to 

ASHRAE 62-89 self-draining standards, with 3/4” NPTI 
copper, ridged mount connection.

INDOOR (EVAPORATOR) FAN ASSEMBLY

1.

Fan shall be direct drive, multi-speed design. Job site 
selected (BHP) brake horse power shall not exceed the 
motors nameplate horse power rating.

2.

Fan wheel shall be double-inlet type with forward-curved 
blades, dynamically balanced to operate smoothly 
throughout the entire range of operation. Airflow design 
shall be constant air volume.

3.

Bearings shall be sealed and permanently lubricated for 
longer life and no maintenance.

4.

Fan assembly shall be “Slip Track” (slide-out) design for 
easy removal and cleaning.

OUTDOOR (CONDENSER) FAN ASSEMBLY

1.

The outdoor fan shall be of the direct-driven propeller type, 
discharge air vertically, have aluminum blades riveted to 
corrosion resistant steel spider bracket and shall be 
statically balanced for smooth operation.

2.

The outdoor fan motor shall be totally enclosed with 
permanently lubricated bearings and internally protected 
against overload conditions.

REFRIGERANT COMPONENTS

1.

Compressors:

a. Shall be fully hermetic reciprocating type, direct drive,

internally protected with internal high-pressure relief and
over temperature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of + or -
10% of the unit nameplate voltage.

b Shall have internal isolation and sound muffling to

minimize vibration and noise, and be externally isolated
on a dedicated, independent mounting.

2.

Coils:

a. Evaporator and condenser coils shall have aluminum

plate fins mechanically bonded to seamless internally-
enhanced copper tubes with all joints brazed.

b Evaporator and Condenser coils shall be of the direct

expansion, draw-thru design.

3.

Refrigerant Circuit and Refrigerant Safety Components 
shall include:

a. Independent fixed-orifice expansion devices.

b. Filter/strainer to eliminate any foreign matter.

c. Accessible service gauge connections on both suction

and discharge lines to charge, evacuate, and measure
refrigerant pressure during any necessary servicing or
troubleshooting, without losing charge and without
disrupting condenser or evaporator air flow.

d The refrigeration system shall provide at least 10° F of

liquid sub-cooling at design conditions.

Summary of Contents for AFFINITY 360101-XTG-A-0108

Page 1: ...needs to carry less inventory LOWER INSTALLATION COST Installation time and costs are reduced by easy power and control wiring connections The small base dimension means less space is required on the...

Page 2: ...2 TON DEB018 6 4 COOLING CAPACITIES 2 TON DEB024 7 5 COOLING CAPACITIES 2 1 2 TON DEB030 8 6 COOLING CAPACITIES 3 TON DEB036 9 7 COOLING CAPACITIES 3 1 2 TON DEB042 10 8 COOLING CAPACITIES 4 TON DEB0...

Page 3: ...condenser fan does not disrupt neighboring areas and does not dry out vegetation surrounding the unit The warm air from the top mounted fan is blown up away from the structure and any landscaping Thi...

Page 4: ...ed side return and unit mounted down shot return applications Damper capable of providing 0 thru 50 of outdoor air field supplied Closes on power loss includes hood and screen assembly RECTANGLE TO RO...

Page 5: ...0 2 400 2 400 2 400 2 800 2 800 CONDENSER COIL ROWS DEEP 1 1 1 1 1 1 1 FINS PER INCH 18 16 20 18 16 13 20 FACE AREA Sq Ft 8 3 8 3 8 3 8 3 11 7 16 4 16 4 CHARGE REFRIGERANT 22 lbs oz 3 4 3 5 3 13 3 10...

Page 6: ...6 17 2 16 5 14 4 14 9 Total Power Input kW 1 99 2 00 1 96 1 94 2 05 2 06 2 02 2 00 2 11 2 12 2 08 2 06 2 14 2 15 2 10 2 09 2 16 2 17 2 13 2 11 Sensible Capacity MBH 1 Entering Dry Bulb F 86 8 7 12 0 1...

Page 7: ...9 7 19 7 Total Power Input kW 2 61 2 58 2 55 2 51 2 67 2 64 2 60 2 56 2 72 2 69 2 65 2 62 2 87 2 84 2 79 2 76 3 01 2 98 2 93 2 90 Sensible Capacity MBH 1 Entering Dry Bulb F 86 13 4 16 7 17 9 17 9 14...

Page 8: ...Power Input kW 3 38 3 28 3 22 3 22 3 45 3 35 3 29 3 28 3 52 3 42 3 36 3 35 3 66 3 55 3 49 3 48 3 79 3 68 3 62 3 61 Sensible Capacity MBH 1 Entering Dry Bulb F 86 16 5 21 3 22 2 22 3 18 5 23 4 23 1 23...

Page 9: ...ut kW 4 05 3 92 3 93 3 85 4 07 3 94 3 95 3 87 4 09 3 96 3 97 3 89 4 15 4 02 4 02 3 95 4 21 4 08 4 08 4 00 Sensible Capacity MBH 1 Entering Dry Bulb F 86 17 5 23 3 25 0 24 4 19 9 26 3 26 6 26 0 22 3 29...

Page 10: ...20 4 22 4 47 4 35 4 27 4 29 4 54 4 42 4 34 4 35 4 69 4 57 4 48 4 50 4 84 4 71 4 63 4 64 Sensible Capacity MBH 1 Entering Dry Bulb F 86 22 4 29 3 30 8 31 2 24 8 32 1 32 0 32 4 27 3 34 9 33 1 33 6 29 3...

Page 11: ...21 5 21 5 49 5 43 5 34 5 33 5 62 5 55 5 46 5 45 5 72 5 66 5 56 5 55 5 83 5 76 5 66 5 65 Sensible Capacity MBH 1 Entering Dry Bulb F 86 27 0 33 2 37 8 37 4 29 6 36 1 38 3 37 9 32 3 39 1 38 8 38 3 34 3...

Page 12: ...58 7 07 6 90 6 79 6 75 7 25 7 06 6 96 6 91 7 47 7 28 7 17 7 12 7 69 7 50 7 38 7 33 Sensible Capacity MBH 1 Entering Dry Bulb F 86 33 5 42 4 45 0 45 3 37 5 47 1 46 9 47 2 41 4 51 8 48 8 49 1 44 9 53 7...

Page 13: ...1205 576 1094 547 Medium 1674 614 1590 590 1506 567 1400 535 1295 502 1190 470 1063 428 Low 1579 567 1512 546 1444 525 1377 504 1282 476 1188 447 1093 418 048 4 0 High 1985 870 1939 850 1897 830 1813...

Page 14: ...Model No Stage KW Total AMPS 018 208 230 1 60 9 0 48 0 1 1 2 6 2NH04500506 1 3 8 5 0 18 1 20 8 25 8 29 3 30 30 30 30 2NH04500706 2 5 6 7 5 27 1 31 3 37 1 42 3 40 45 40 45 024 208 230 1 60 11 2 60 0 1...

Page 15: ...hange without notice Certified dimensions will be provided upon request UNIT CONDENSATE CONNECTION NPTI TRAP REQUIRED OVERALL SIDE SUPPLY AIR OPENING SIDE RETURN AIR OPENING COMPRESSOR SERVICE ACCESS...

Page 16: ...Shipping Weight Operating Weight Corner Weights Economizer lbs Roof Curb lbs A B C D 018 318 313 86 76 73 83 40 8 70 14 75 024 324 319 88 77 75 85 030 333 328 85 81 82 86 036 338 333 91 80 78 88 042...

Page 17: ...OWER SUPPLY SUPPLY AIR DUCT RETURN AIR DUCT FIELD SUPPLIED DISCONNECT SWITCH LOCATED TO REAR OF UNIT CONTROL WIRING TO INDOOR THERMOSTAT SLAB ON GROUND INSTALLATION ROOF CURB INSTALLATION BOTTOM DUCT...

Page 18: ...ED PANELS 22 14 OPENING FOR RETURN AIR DUCT OPENING FOR SUPPLY AIR DUCT RECOMMENDED DUCT SIZE SUPPLY AIR DUCT x RETURN AIR DUCT x UNIT BASE RAIL UNIT BASE WOOD NAILER 8 MIN ABOVE FINISHED ROOF CURB FR...

Page 19: ...trols Unitary Products 19 FIGURE 9 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY DEB MODELS 15695BASH0301 SEE DETAIL A T2 M1 2 DETAIL A BLK BLK CCH L1 T1 OPTIONAL CCH S P CONFIGURATION BLK BLK CCH...

Page 20: ...tandard 24 O C beams without modification to building structure duct work and base unit 10 Condensate pan shall be internally sloped and conform to ASHRAE 62 89 self draining standards with 3 4 NPTI c...

Page 21: ...section shall have a primary limit control s and automatic reset to prevent the heating element system from operating at an excessive temperature 3 The heating section assembly shall slide out of the...

Page 22: ...360101 XTG A 0108 22 Johnson Controls Unitary Products...

Page 23: ...360101 XTG A 0108 Johnson Controls Unitary Products 23...

Page 24: ...hout notice Printed in U S A 360101 XTG A 0108 Copyright 2008 by Johnson Controls Inc All rights reserved Supersedes 263146 XTG A 0206 036 21753 001 A 0206 Johnson Controls Unitary Products 5005 York...

Reviews: