Over/Under Voltage Shutdown -

 An over/under voltage condition 

exists when the control voltage is outside the range of 18 VAC to 
30 VAC. If the over/under voltage shutdown lasts for 15 minutes, 
the lockout and alarm relay will be energized. Over/under voltage 
shutdown is self-resetting in that if the voltage comes back within 
range of 18 VAC to 30 VAC for at least 0.5 seconds, then normal 
operation is restored.

Operation Description

Power Up -

 The unit will not operate until all the inputs and safety 

controls are checked for normal conditions. The unit has a 5 to 80 
second random start delay at power up. Then the compressor has 
a 4 minute anti-short cycle delay after the random start delay.

Standby In standby mode, Y1, Y2, W, DH, and G are not active. 
Input O may be active. The blower and compressor will be off.

Heating Operation

Heating, 1st Stage (Y1) -

 The blower is started on “G” speed 

immediately and the compressor is energized 10 seconds after 
the Y1 input is received. The ECM blower motor is switched to low 
speed 15 seconds after the Y1 input.

Heating, 2nd Stage (Y1, Y2) -

 The compressor will be staged to 

full capacity 20 seconds after Y2 input is received. The ECM blower 
will shift to high speed 15 seconds after the Y2 input is received.

Heating, 3rd Stage (Y1, Y2, W) - 

The hot water pump is de-

energized and the first stage of electric heat is energized 10 
seconds after the W command is received. If the demand 
continues the second stage of electric heat will be energized after 
5 minutes.

Emergency Heat (W) -

 The blower will be started on “G” speed, 

10 seconds later the first stage of electric heat will be turned on. 5 
seconds after the first stage of electric heat is energized the blower 
will shift to Aux speed. If the emergency heat demand is not satisfied 
after 2 minutes the second electric heat stage will be energized.

Blower (G) - 

The blower will start immediately upon receiving 

a thermostat G command. If there are no other commands 
from the thermostat the ECM will run on “G” speed until the G 
command is removed. Regardless of blower input (G) from the 
thermostat, the blower will remain on for 30 seconds at the end 
of each heating cycle.

Cooling Operation

In all cooling operations, the reversing valve directly tracks the O 
input. Thus, anytime the O input is present, the reversing valve will 
be energized.

Cooling, 1st Stage (Y1, O) - 

The blower is started on “G” speed 

immediately and the compressor is energized 10 seconds after the Y1 
input is received. The ECM blower motor is switched to low speed 15 
seconds after the Y1 input.

Cooling, 2nd Stage (Y1, Y2, O) - 

The compressor will be staged to 

full capacity 20 seconds after Y2 input is received. The ECM blower 
will shift to high speed 15 seconds after the Y2 input is received.

Blower (G) -

 The blower will start immediately upon receiving a 

thermostat G command. If there are no other commands from the 
thermostat the ECM will run on “G” speed until the G command is 
removed. Regardless of blower input (G) from the thermostat, the 
blower will remain on for 30 seconds at the end of each heating, 
cooling, and emergency heat cycle.

Dehumidification (Y1, O, DH or Y1, Y2, O, DH) -

 When a DH 

command is received from the thermostat during a compressor 
call for cooling the ECM blower speed will be reduced by 15% to 
increase dehumidification.

Emergency Shutdown -

 Four (4) seconds after a valid ES input, 

P2-7 is present, all control outputs will be turned off and remain 
off until the emergency shutdown input is no longer present. The 
first time that the compressor is started after the control exits 
the emergency shutdown mode, there will be an anti-short cycle 
delay followed by a random start delay. Input must be tied to 
common to activate.

Continuous Blower Operation -

 The blower output will be 

energized any time the control has a G input present, unless the 
control has an emergency shutdown input present. The blower 
output will be turned off when G input is removed.

Load Shed -

 The LS input disables all outputs with the exception 

of the blower output. When the LS input has been cleared, the anti-
short cycle timer and random start timer will be initiated. Input must 
be tied to common to activate.

Controls - Aurora Base Control cont.

LX ULTRA SERIES INSTALLATION MANUAL

Summary of Contents for 33p502-05

Page 1: ...70 75 THRU 6 NOMINAL TONS Due to continuous product improvement specifications are subject to change without notice Visit us on the web at www yorkgeothermal com Additional rating information can foun...

Page 2: ......

Page 3: ...17 Freeze Detection 18 Electrical Connections 18 Electrical Data 19 21 Blower Performance Data 21 27 Wiring Schematics 28 29 Controls Aurora Base Control 30 33 Unit Startup 34 Operating Limits and Op...

Page 4: ...n 0 Composite No Secondary Connection 1 Composite Secondary Connection 2 Stainless Steel No Secondary Connection 3 Stainless Steel Secondary Connection Cabinet Option 0 Unpainted 1 in MERV 4 Filter Ra...

Page 5: ...ing the units from the packaging if necessary Units in question should also be internally inspected If any damage is noted the carrier should make the proper notation on the delivery receipt acknowled...

Page 6: ...open return applications Deluxe filter rack for ductable return applications 2 61 cm Service Access Left Return Right Return opposite side 2 61 cm Alternate Service Access Field installed duct flange...

Page 7: ...uct flange installed 0 10 in Return Connection using deluxe filter rack 0 10 in M N P Q R S T U V W Filter Rack Width Supply Width Supply Depth Return Depth Return Height 009 012 in 2 2 10 0 10 0 6 1...

Page 8: ...E AIR COIL SIDE 0 5 in 1 3 cm knockout 1 in 2 5 cm knockout 1 in 2 5 cm knockout 0 5 in 1 3 cm knockout BP BP FILTER RACK FILTER RACK Standard filter rails Standard filter rails Deluxe filter rack opt...

Page 9: ...8 0 8 1 9 2 9 1 cm 64 8 134 6 53 8 4 6 17 3 2 0 25 4 mm 23 4 23 1 070 in 25 5 61 0 21 2 1 8 6 8 0 8 1 9 2 9 1 cm 64 8 154 9 53 8 4 6 17 3 2 0 25 4 mm 23 4 23 1 Horizontal Models Discharge Connection...

Page 10: ...a double nut is required since vibration could loosen a single nut To allow filter access install hanger brackets as illustrated in the Hanger Bracket Locations section The unit should be pitched app...

Page 11: ...8 28 1 24 4 cm 157 0 71 4 62 0 10 29 13 Weight Distribution Model Vertical Shipping Weight Horizontal Shipping Weight Horizontal Weight Distribution Front Back D E F G 009 lb 110 120 46 23 26 25 kg 50...

Page 12: ...t whenever the unit operates To assure proper flow use pressure temperature ports to determine the flow rate These ports should be located at the supply and return water connections on the unit The pr...

Page 13: ...han 0 5 ppm Less than 0 5 ppm Ammonia Nitrate Less than 0 5 ppm Less than 0 5 ppm Less than 0 5 ppm Ammonia Hydroxide Less than 0 5 ppm Less than 0 5 ppm Less than 0 5 ppm Ammonia Sulfate Less than 0...

Page 14: ...t the system from dirty water conditions Dirty water will result in system wide degradation of performance and solids may clog valves strainers flow regulators etc Additionally the heat exchanger may...

Page 15: ...ow Open System Groundwater Application Flexible Duct Collar Vibration Absorbing Pad P T Plugs Drain Hot Water Generator Connections Low Voltage to Thermostat and Valve Unit Supply Aux Heat Supply Wate...

Page 16: ...the water heater tank 4 Drain the tank by opening the valve on the bottom of the tank then open the pressure relief valve or hot water faucet 5 Flush the tank by opening the cold water inlet valve to...

Page 17: ...st the temperature setting on the tank On tanks with both upper and lower elements the lower element should be turned down to the lowest setting approximately 100 F The upper element should be adjuste...

Page 18: ...factory wired for 230 volt operation For 208 volt operation the red and blue transformer wires must be switched on terminal strip PS CAUTION When installing a unit with an ECM blower motor in 460 60...

Page 19: ...2 60 0 n a 2 0 13 2 16 0 25 208 230 60 3 187 253 13 9 8 9 58 0 34 8 2 2 11 1 13 3 20 460 60 3 414 506 6 5 4 2 28 0 16 8 1 1 5 3 6 4 10 15 036 208 230 60 1 187 253 27 0 17 3 96 7 38 7 2 2 19 5 23 8 40...

Page 20: ...9 8 9 58 0 34 8 4 1 13 0 15 2 20 460 60 3 414 506 6 5 4 2 28 0 16 8 2 1 6 3 7 4 10 15 036 208 230 60 1 187 253 27 0 17 3 96 7 38 7 4 1 21 4 25 7 40 265 60 1 238 292 19 0 12 2 72 0 n a 3 6 15 8 18 9 3...

Page 21: ...15 036 208 230 60 1 187 253 27 0 17 3 96 7 38 7 4 0 21 3 25 6 40 265 60 1 238 292 19 0 12 2 72 0 n a 4 1 16 3 19 3 30 208 230 60 3 187 253 20 0 12 8 95 0 57 0 4 0 16 8 20 0 30 460 60 3 414 506 10 0 6...

Page 22: ...1485 1445 1410 1310 1215 1130 1030 L 1180 1170 1160 1140 1120 1100 1080 1050 1020 970 930 875 060 H 11 x 10 1 2360 2330 2300 2270 2240 2215 2190 2160 2130 2095 2060 1985 1920 1855 M 2165 2130 2095 207...

Page 23: ...23 Setting Blower Speed PSC CAUTION Disconnect all power before performing this operation PSC BLOWER MOTOR BODY HIGH LOW MEDIUM F A N S P E E D W I R E LX ULTRA SERIES INSTALLATION MANUAL...

Page 24: ...85 1250 1220 1190 1158 1125 1085 1045 960 Med High 4 1265 1253 1240 1220 1200 1175 1150 1120 1090 1053 1015 Med 3 1160 1143 1125 1113 1100 1085 1070 1055 1040 1020 1000 Med Low 2 1110 1095 1080 1065 1...

Page 25: ...nnects Line 1 orange wire to L Ground green wire to G Line 2 for 208V 230V units to N brown wire Signal Connection 1 4 in quick connects Common to C 24VAC to Taps 1 5 Applying 24VAC power between any...

Page 26: ...1300 1500 1600 1800 L M H 048 0 50 650 750 850 950 1050 1150 1250 1325 1375 1475 1550 1600 L M H 048 w 1hp 0 75 800 1000 1100 1300 1500 1600 1800 L M H 060 0 75 750 900 1000 1200 1400 1600 1700 1850 2...

Page 27: ...reen displays the current variable speed ECM settings It allows the technician to enter the setup screens to change the variable speed ECM settings Change the highlighted item using the and buttons an...

Page 28: ...h Pressure Lockout Low Pressure Lockout Low Water Coil Limit Lockout FP1 Low Air Coil Limit Lockout FP2 Reserved Condensate Overflow Lockout Over Under Voltage Shutdown Reserved Reserved Air Water Coi...

Page 29: ...3 Red 32 Black 35 Black White Black White Yellow LED4 LED5 G G Note 5 Note 6 Slow Flash Fast Flash Flash Code Status LED LED1 Green Configuration LED LED2 Yellow Fault LED LED3 Red Status LED LED1 Gre...

Page 30: ...one time Test mode will automatically time out after 30 minutes Test mode can be exited by pressing and holding the SW1 button for 2 to 5 seconds or by cycling the power NOTE Test mode will automatica...

Page 31: ...ed shall flash the fault code To reset lockout conditions with SW2 8 On thermostat inputs Y1 Y2 and W must be removed for at least 3 seconds To reset lockout conditions with SW2 8 Off thermostat input...

Page 32: ...command is removed Regardless of blower input G from the thermostat the blower will remain on for 30 seconds at the end of each heating cycle Cooling Operation In all cooling operations the reversing...

Page 33: ...plugs into the exterior of the cabinet in the AID Tool port ABC Control Board Layout Aurora Base Control LED Displays These three LEDs display the status configuration and fault codes for the control...

Page 34: ...easuring the pressure drop through the heat exchanger using the P T plugs and comparing to the pressure drop table 6 Check the temperature of both the supply and discharge water Refer to Unit Operatin...

Page 35: ...375 10 14 7 11 7 10 28 34 90 1 5 170 177 425 460 14 18 12 16 8 11 42 50 3 0 174 181 435 470 14 18 12 16 8 11 42 50 110 2 3 3 0 11 10 09 NOTES Cooling performance based on entering air temperatures of...

Page 36: ...6 14 0 9 1 8 8 8 5 8 2 7 9 048 6 0 2 0 1 7 1 3 1 0 0 6 9 0 4 2 3 8 3 5 3 1 2 7 12 0 6 7 6 3 5 9 5 6 5 2 16 0 11 5 11 2 10 8 10 5 10 1 060 9 0 3 6 3 3 3 0 2 7 2 3 12 0 6 1 5 8 5 5 5 2 4 8 15 0 9 6 9 2...

Page 37: ...Bad Valves Low High Low High Normal High Low Low TXV Bulb Loss of Charge Low Low Low High High Low Low Scaled Coaxial Heat Exchanger Heating Low Low Low Normal Low High Low Low Scaled Coaxial Heat Exc...

Page 38: ...5 1 13 1 31 1 07 1 23 0 83 0 91 4 43 4 90 n a 041 042 0 49 1 03 1 29 1 49 n a 0 81 1 05 4 33 4 99 5 11 5 64 048 0 51 0 58 1 36 1 57 n a 0 91 1 05 3 60 4 14 4 16 4 78 060 0 29 0 34 0 76 0 87 n a 0 56 0...

Page 39: ...26 2 31 4 32 2 31 6 30 8 29 7 030 4 0 18 9 25 9 32 9 35 2 35 4 37 0 6 0 14 5 19 9 27 0 33 4 35 1 37 2 37 6 37 6 34 7 8 0 15 2 20 9 28 0 34 0 35 2 39 1 39 7 37 9 35 0 036 5 0 24 6 33 0 41 7 47 4 45 3...

Page 40: ...place the compressor If sufficient cooling or heating is not obtained 1 Check control for improper location or setting 2 Check for restriction in water flow 3 Check refrigerant subcooling and superhea...

Page 41: ...__ AMPS n ______ AMPS Watts m x n x 0 85 o _____ WATTS o ______ WATTS 6 CAPACITY Cooling Capacity HR o x 3 413 p _____ btu hr Heating Capacity HE o x 3 413 p _____ btu hr 7 EFFICIENCY Cooling EER p o...

Page 42: ...ltage Loop Open Unit Amp Draw Closed COAX SOURCE HEA7 1 ANALYSIS EXPANSION VALVE F AIR COIL F COMPRESSOR DISCHARGE SUCTION Subcooling Superheat REVERSING VALVE PSI F SAT F PSI SAT F F F LIQUID LINE Li...

Page 43: ...e Drain In areas where airborne bacteria produce a slime in the drain pan it may be necessary to treat chemically to minimize the problem The condensate drain can pick up lint and dirt especially with...

Page 44: ...14S553 02 Not Available High Static VS ECM Blower Housing Not Available 53P515B01 53P515B01 Not Available PSC Motor Blower PSC Motor 208 230 60 1 14P506 02 14P507B01 14P508B01 14P509B01 14P510B01 14P5...

Page 45: ...ailable High Static VS ECM Blower Housing Not Available 53P515B01 53P515B01 Not Available PSC Motor Blower PSC Motor 208 230 60 1 14P506 02 14P507B01 14P508B01 14P509B01 14P510B01 14P511B01 14P512B01...

Page 46: ...46 Revision Guide Pages Description Date By All First Published 18 Oct 2013 DS LX ULTRA SERIES INSTALLATION MANUAL...

Page 47: ......

Page 48: ...t LX Ultra Series Type Geothermal Water Source Heat Pumps Size 0 75 6 Ton Document Type Installation Manual Part Number IM1200AK6 Release Date 10 13 2013 The manufacturer has a policy of continual pro...

Reviews: