Blower Performance Data cont.

5-Speed ECM Motor

Factory settings are in Bold

Air

fl

 ow values are with dry coil and standard 1 in. 

fi

 lter

ISO/AHRI rating point on the US*070 will require moving the red wire on the motor to high speed (tap 5) and disconnecting the tan wire from tap 5.

5-Speed ECM Motor 
Connections

CAUTION: Disconnect all power before 
performing this operation.

Setting Blower Speed - 5-Speed ECM

5-speed ECM blower motors have 

fi

 ve (5) speeds of which 

three (3) are selectable on single speed and four (4) are 
selectable on dual capacity.

Model

Motor     

Speed

Motor     

Tap

Blower 

Size

Motor     

HP

Airflow (cfm) at External Static Pressure (in. wg)

0

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50

0.60

0.70

0.80

0.90

1.00

015

High

5

9 x 7

1/2

915

895

880

865

850

830

815

805

795

775

750

730

695

640

-

-

Med High

4

805

785

765

750

740

725

705

685

665

655

635

605

535

-

-

-

Med

3

725

715

700

680

660

635

615

600

585

560

535

485

-

-

-

-

Med Low

2

695

675

650

630

610

590

575

550

525

490

455

-

-

-

-

-

Low

1

655

600

550

530

508

490

475

435

395

350

-

-

-

-

-

-

018

High

5

9 x 7

1/2

915

895

880

865

850

830

815

805

795

775

750

730

695

640

-

-

Med High

4

805

785

765

750

740

725

705

685

665

655

635

605

535

-

-

-

Med

3

725

715

700

680

660

635

615

600

585

560

535

485

-

-

-

-

Med Low

2

695

675

650

630

610

590

575

550

525

490

455

-

-

-

-

-

Low

1

655

600

550

530

508

490

475

435

395

350

-

-

-

-

-

-

023

High

5

9 x 7

1/2

980

960

940

930

920

905

890

875

860

840

820

800

745

-

-

-

Med High

4

890

878

865

845

825

813

800

785

770

753

735

710

665

-

-

-

Med

3

830

815

800

788

775

755

735

723

710

690

670

640

600

-

-

-

Med Low

2

780

760

740

703

665

653

640

620

600

585

570

-

-

-

-

-

Low

1

625

593

560

535

510

495

480

455

430

410

390

-

-

-

-

-

024

High

5

9 x 7

1/2

980

960

940

930

920

905

890

875

860

840

820

800

745

-

-

-

Med High

4

890

878

865

845

825

813

800

785

770

753

735

710

665

-

-

-

Med

3

830

815

800

788

775

755

735

723

710

690

670

640

600

-

-

-

Med Low

2

780

760

740

703

665

653

640

620

600

585

570

-

-

-

-

-

Low

1

625

593

560

535

510

495

480

455

430

410

390

-

-

-

-

-

030

High

5

9 x 7

1/2

1340

1310

1280

1240

1200

1170

1140

1095

1050

1015

980

900

800

-

-

-

Med High

4

1130

1115

1100

1085

1070

1057

1044

1022

1000

970

940

870

780

-

-

-

Med

3

1030

1005

980

965

950

935

920

900

880

870

860

830

750

-

-

-

Med Low

2

960

945

930

915

900

885

870

855

840

825

810

790

740

-

-

-

Low

1

790

765

740

725

710

690

670

660

650

630

610

580

500

-

-

-

036

High

5

9 x 7

1/2

1370

1345

1320

1285

1250

1220

1190

1158

1125

1085

1045

960

-

-

-

-

Med High

4

1265

1253

1240

1220

1200

1175

1150

1120

1090

1053

1015

-

-

-

-

-

Med

3

1160

1143

1125

1113

1100

1085

1070

1055

1040

1020

1000

-

-

-

-

-

Med Low

2

1110

1095

1080

1065

1050

1038

1025

1008

990

980

970

-

-

-

-

-

Low

1

825

803

780

770

760

740

720

705

690

670

650

-

-

-

-

-

041

High

5

11 x 10

1

1840

1825

1810

1790

1770

1745

1720

1700

1680

1660

1640

1600

1570

1530

1480

-

Med High

4

1730

1713

1695

1670

1645

1623

1600

1575

1550

1535

1520

1480

1440

1390

1350

-

Med

3

1630

1610

1590

1563

1535

1513

1490

1470

1450

1425

1400

1370

1330

1290

-

-

Med Low

2

1550

1520

1490

1465

1440

1415

1390

1370

1350

1330

1310

1260

1220

1180

-

-

Low

1

1380

1340

1300

1275

1250

1225

1200

1175

1150

1125

1100

1030

980

820

-

-

042

High

5

11 x 10

1

1840

1825

1810

1790

1770

1745

1720

1700

1680

1660

1640

1600

1570

1530

1480

-

Med High

4

1730

1713

1695

1670

1645

1623

1600

1575

1550

1535

1520

1480

1440

1390

1350

-

Med

3

1630

1610

1590

1563

1535

1513

1490

1470

1450

1425

1400

1370

1330

1290

-

-

Med Low

2

1550

1520

1490

1465

1440

1415

1390

1370

1350

1330

1310

1260

1220

1180

-

-

Low

1

1380

1340

1300

1275

1250

1225

1200

1175

1150

1125

1100

1030

980

820

-

-

048

High

5

11 x 10

1

2060

2045

2030

2015

2000

1970

1940

1925

1910

1890

1870

1830

1800

1750

1740

-

Med High

4

1880

1860

1840

1825

1810

1785

1760

1740

1720

1705

1690

1640

1610

1570

1535

-

Med

3

1790

1770

1750

1730

1710

1685

1660

1640

1620

1600

1580

1550

1510

1460

-

-

Med Low

2

1670

1650

1630

1605

1580

1555

1530

1510

1490

1470

1450

1410

1370

1340

-

-

Low

1

1430

1405

1380

1353

1325

1303

1280

1255

1230

1210

1190

1130

1070

925

-

-

060

High

5

11 x 10

1

2400

2360

2330

2315

2300

2290

2285

2275

2265

2250

2230

2200

2165

2110

2080

2030

Med High

4

2180

2160

2140

2130

2120

2105

2090

2075

2060

2045

2030

2000

1960

1930

1890

1850

Med

3

2080

2050

2020

2010

2000

1985

1970

1955

1940

1925

1910

1870

1840

1800

1760

1720

Med Low

2

1930

1920

1910

1893

1875

1863

1850

1833

1815

1798

1780

1740

1700

1660

1620

1590

Low

1

1750

1735

1720

1698

1675

1658

1640

1620

1600

1583

1565

1525

1490

1450

1410

1350

070

High

5

11 x 10

1

2400

2360

2330

2315

2300

2290

2285

2275

2265

2250

2230

2200

2165

2110

2080

2030

Med High

4

2180

2160

2140

2130

2120

2105

2090

2075

2060

2045

2030

2000

1960

1930

1890

1850

Med

3

2080

2050

2020

2010

2000

1985

1970

1955

1940

1925

1910

1870

1840

1800

1760

1720

Med Low

2

1930

1920

1910

1893

1875

1863

1850

1833

1815

1798

1780

1740

1700

1660

1620

1590

Low

1

1750

1735

1720

1698

1675

1658

1640

1620

1600

1583

1565

1525

1490

1450

1410

1350

01/23/13

LX ULTRA SERIES INSTALLATION MANUAL

Summary of Contents for 33p502-05

Page 1: ...70 75 THRU 6 NOMINAL TONS Due to continuous product improvement specifications are subject to change without notice Visit us on the web at www yorkgeothermal com Additional rating information can foun...

Page 2: ......

Page 3: ...17 Freeze Detection 18 Electrical Connections 18 Electrical Data 19 21 Blower Performance Data 21 27 Wiring Schematics 28 29 Controls Aurora Base Control 30 33 Unit Startup 34 Operating Limits and Op...

Page 4: ...n 0 Composite No Secondary Connection 1 Composite Secondary Connection 2 Stainless Steel No Secondary Connection 3 Stainless Steel Secondary Connection Cabinet Option 0 Unpainted 1 in MERV 4 Filter Ra...

Page 5: ...ing the units from the packaging if necessary Units in question should also be internally inspected If any damage is noted the carrier should make the proper notation on the delivery receipt acknowled...

Page 6: ...open return applications Deluxe filter rack for ductable return applications 2 61 cm Service Access Left Return Right Return opposite side 2 61 cm Alternate Service Access Field installed duct flange...

Page 7: ...uct flange installed 0 10 in Return Connection using deluxe filter rack 0 10 in M N P Q R S T U V W Filter Rack Width Supply Width Supply Depth Return Depth Return Height 009 012 in 2 2 10 0 10 0 6 1...

Page 8: ...E AIR COIL SIDE 0 5 in 1 3 cm knockout 1 in 2 5 cm knockout 1 in 2 5 cm knockout 0 5 in 1 3 cm knockout BP BP FILTER RACK FILTER RACK Standard filter rails Standard filter rails Deluxe filter rack opt...

Page 9: ...8 0 8 1 9 2 9 1 cm 64 8 134 6 53 8 4 6 17 3 2 0 25 4 mm 23 4 23 1 070 in 25 5 61 0 21 2 1 8 6 8 0 8 1 9 2 9 1 cm 64 8 154 9 53 8 4 6 17 3 2 0 25 4 mm 23 4 23 1 Horizontal Models Discharge Connection...

Page 10: ...a double nut is required since vibration could loosen a single nut To allow filter access install hanger brackets as illustrated in the Hanger Bracket Locations section The unit should be pitched app...

Page 11: ...8 28 1 24 4 cm 157 0 71 4 62 0 10 29 13 Weight Distribution Model Vertical Shipping Weight Horizontal Shipping Weight Horizontal Weight Distribution Front Back D E F G 009 lb 110 120 46 23 26 25 kg 50...

Page 12: ...t whenever the unit operates To assure proper flow use pressure temperature ports to determine the flow rate These ports should be located at the supply and return water connections on the unit The pr...

Page 13: ...han 0 5 ppm Less than 0 5 ppm Ammonia Nitrate Less than 0 5 ppm Less than 0 5 ppm Less than 0 5 ppm Ammonia Hydroxide Less than 0 5 ppm Less than 0 5 ppm Less than 0 5 ppm Ammonia Sulfate Less than 0...

Page 14: ...t the system from dirty water conditions Dirty water will result in system wide degradation of performance and solids may clog valves strainers flow regulators etc Additionally the heat exchanger may...

Page 15: ...ow Open System Groundwater Application Flexible Duct Collar Vibration Absorbing Pad P T Plugs Drain Hot Water Generator Connections Low Voltage to Thermostat and Valve Unit Supply Aux Heat Supply Wate...

Page 16: ...the water heater tank 4 Drain the tank by opening the valve on the bottom of the tank then open the pressure relief valve or hot water faucet 5 Flush the tank by opening the cold water inlet valve to...

Page 17: ...st the temperature setting on the tank On tanks with both upper and lower elements the lower element should be turned down to the lowest setting approximately 100 F The upper element should be adjuste...

Page 18: ...factory wired for 230 volt operation For 208 volt operation the red and blue transformer wires must be switched on terminal strip PS CAUTION When installing a unit with an ECM blower motor in 460 60...

Page 19: ...2 60 0 n a 2 0 13 2 16 0 25 208 230 60 3 187 253 13 9 8 9 58 0 34 8 2 2 11 1 13 3 20 460 60 3 414 506 6 5 4 2 28 0 16 8 1 1 5 3 6 4 10 15 036 208 230 60 1 187 253 27 0 17 3 96 7 38 7 2 2 19 5 23 8 40...

Page 20: ...9 8 9 58 0 34 8 4 1 13 0 15 2 20 460 60 3 414 506 6 5 4 2 28 0 16 8 2 1 6 3 7 4 10 15 036 208 230 60 1 187 253 27 0 17 3 96 7 38 7 4 1 21 4 25 7 40 265 60 1 238 292 19 0 12 2 72 0 n a 3 6 15 8 18 9 3...

Page 21: ...15 036 208 230 60 1 187 253 27 0 17 3 96 7 38 7 4 0 21 3 25 6 40 265 60 1 238 292 19 0 12 2 72 0 n a 4 1 16 3 19 3 30 208 230 60 3 187 253 20 0 12 8 95 0 57 0 4 0 16 8 20 0 30 460 60 3 414 506 10 0 6...

Page 22: ...1485 1445 1410 1310 1215 1130 1030 L 1180 1170 1160 1140 1120 1100 1080 1050 1020 970 930 875 060 H 11 x 10 1 2360 2330 2300 2270 2240 2215 2190 2160 2130 2095 2060 1985 1920 1855 M 2165 2130 2095 207...

Page 23: ...23 Setting Blower Speed PSC CAUTION Disconnect all power before performing this operation PSC BLOWER MOTOR BODY HIGH LOW MEDIUM F A N S P E E D W I R E LX ULTRA SERIES INSTALLATION MANUAL...

Page 24: ...85 1250 1220 1190 1158 1125 1085 1045 960 Med High 4 1265 1253 1240 1220 1200 1175 1150 1120 1090 1053 1015 Med 3 1160 1143 1125 1113 1100 1085 1070 1055 1040 1020 1000 Med Low 2 1110 1095 1080 1065 1...

Page 25: ...nnects Line 1 orange wire to L Ground green wire to G Line 2 for 208V 230V units to N brown wire Signal Connection 1 4 in quick connects Common to C 24VAC to Taps 1 5 Applying 24VAC power between any...

Page 26: ...1300 1500 1600 1800 L M H 048 0 50 650 750 850 950 1050 1150 1250 1325 1375 1475 1550 1600 L M H 048 w 1hp 0 75 800 1000 1100 1300 1500 1600 1800 L M H 060 0 75 750 900 1000 1200 1400 1600 1700 1850 2...

Page 27: ...reen displays the current variable speed ECM settings It allows the technician to enter the setup screens to change the variable speed ECM settings Change the highlighted item using the and buttons an...

Page 28: ...h Pressure Lockout Low Pressure Lockout Low Water Coil Limit Lockout FP1 Low Air Coil Limit Lockout FP2 Reserved Condensate Overflow Lockout Over Under Voltage Shutdown Reserved Reserved Air Water Coi...

Page 29: ...3 Red 32 Black 35 Black White Black White Yellow LED4 LED5 G G Note 5 Note 6 Slow Flash Fast Flash Flash Code Status LED LED1 Green Configuration LED LED2 Yellow Fault LED LED3 Red Status LED LED1 Gre...

Page 30: ...one time Test mode will automatically time out after 30 minutes Test mode can be exited by pressing and holding the SW1 button for 2 to 5 seconds or by cycling the power NOTE Test mode will automatica...

Page 31: ...ed shall flash the fault code To reset lockout conditions with SW2 8 On thermostat inputs Y1 Y2 and W must be removed for at least 3 seconds To reset lockout conditions with SW2 8 Off thermostat input...

Page 32: ...command is removed Regardless of blower input G from the thermostat the blower will remain on for 30 seconds at the end of each heating cycle Cooling Operation In all cooling operations the reversing...

Page 33: ...plugs into the exterior of the cabinet in the AID Tool port ABC Control Board Layout Aurora Base Control LED Displays These three LEDs display the status configuration and fault codes for the control...

Page 34: ...easuring the pressure drop through the heat exchanger using the P T plugs and comparing to the pressure drop table 6 Check the temperature of both the supply and discharge water Refer to Unit Operatin...

Page 35: ...375 10 14 7 11 7 10 28 34 90 1 5 170 177 425 460 14 18 12 16 8 11 42 50 3 0 174 181 435 470 14 18 12 16 8 11 42 50 110 2 3 3 0 11 10 09 NOTES Cooling performance based on entering air temperatures of...

Page 36: ...6 14 0 9 1 8 8 8 5 8 2 7 9 048 6 0 2 0 1 7 1 3 1 0 0 6 9 0 4 2 3 8 3 5 3 1 2 7 12 0 6 7 6 3 5 9 5 6 5 2 16 0 11 5 11 2 10 8 10 5 10 1 060 9 0 3 6 3 3 3 0 2 7 2 3 12 0 6 1 5 8 5 5 5 2 4 8 15 0 9 6 9 2...

Page 37: ...Bad Valves Low High Low High Normal High Low Low TXV Bulb Loss of Charge Low Low Low High High Low Low Scaled Coaxial Heat Exchanger Heating Low Low Low Normal Low High Low Low Scaled Coaxial Heat Exc...

Page 38: ...5 1 13 1 31 1 07 1 23 0 83 0 91 4 43 4 90 n a 041 042 0 49 1 03 1 29 1 49 n a 0 81 1 05 4 33 4 99 5 11 5 64 048 0 51 0 58 1 36 1 57 n a 0 91 1 05 3 60 4 14 4 16 4 78 060 0 29 0 34 0 76 0 87 n a 0 56 0...

Page 39: ...26 2 31 4 32 2 31 6 30 8 29 7 030 4 0 18 9 25 9 32 9 35 2 35 4 37 0 6 0 14 5 19 9 27 0 33 4 35 1 37 2 37 6 37 6 34 7 8 0 15 2 20 9 28 0 34 0 35 2 39 1 39 7 37 9 35 0 036 5 0 24 6 33 0 41 7 47 4 45 3...

Page 40: ...place the compressor If sufficient cooling or heating is not obtained 1 Check control for improper location or setting 2 Check for restriction in water flow 3 Check refrigerant subcooling and superhea...

Page 41: ...__ AMPS n ______ AMPS Watts m x n x 0 85 o _____ WATTS o ______ WATTS 6 CAPACITY Cooling Capacity HR o x 3 413 p _____ btu hr Heating Capacity HE o x 3 413 p _____ btu hr 7 EFFICIENCY Cooling EER p o...

Page 42: ...ltage Loop Open Unit Amp Draw Closed COAX SOURCE HEA7 1 ANALYSIS EXPANSION VALVE F AIR COIL F COMPRESSOR DISCHARGE SUCTION Subcooling Superheat REVERSING VALVE PSI F SAT F PSI SAT F F F LIQUID LINE Li...

Page 43: ...e Drain In areas where airborne bacteria produce a slime in the drain pan it may be necessary to treat chemically to minimize the problem The condensate drain can pick up lint and dirt especially with...

Page 44: ...14S553 02 Not Available High Static VS ECM Blower Housing Not Available 53P515B01 53P515B01 Not Available PSC Motor Blower PSC Motor 208 230 60 1 14P506 02 14P507B01 14P508B01 14P509B01 14P510B01 14P5...

Page 45: ...ailable High Static VS ECM Blower Housing Not Available 53P515B01 53P515B01 Not Available PSC Motor Blower PSC Motor 208 230 60 1 14P506 02 14P507B01 14P508B01 14P509B01 14P510B01 14P511B01 14P512B01...

Page 46: ...46 Revision Guide Pages Description Date By All First Published 18 Oct 2013 DS LX ULTRA SERIES INSTALLATION MANUAL...

Page 47: ......

Page 48: ...t LX Ultra Series Type Geothermal Water Source Heat Pumps Size 0 75 6 Ton Document Type Installation Manual Part Number IM1200AK6 Release Date 10 13 2013 The manufacturer has a policy of continual pro...

Reviews: