Charging Tables
Table 63: ZQ04 Charging Table
Air Flow Indoor Db/Wb
Outdoor DB ° F
Suction P psig
Suction Temp. ° F
Liquid P psig
Liquid Temp. ° F
Delta T Db ° F
Compr. amps
75
126
62
266
77
-24
7.9
85
130
60
310
90
-25
9.0
300 Cfm/Ton 80/62
95
133
57
354
102
-26
10.1
75
126
62
266
77
-24
7.9
85
132
62
312
88
-23
9.0
300 Cfm/Ton 80/67
95
139
62
358
100
-23
10.1
75
126
61
265
76
-25
7.9
85
135
63
314
87
-22
9.0
300 Cfm/Ton 80/72
95
144
66
362
98
-19
10.1
75
122
58
263
78
-22
7.9
85
127
57
308
90
-22
8.9
300 Cfm/Ton 75/62
95
132
55
353
102
-22
10.0
75
128
65
267
77
-22
7.9
85
133
63
313
89
-22
9.0
400 Cfm/Ton 80/62
95
138
62
358
100
-22
10.1
75
128
65
268
76
-21
7.9
85
135
65
314
88
-21
9.0
400 Cfm/Ton 80/67
95
142
65
361
99
-20
10.2
75
129
65
268
76
-21
7.9
85
137
66
316
87
-19
9.0
400 Cfm/Ton 80/72
95
146
68
363
98
-18
10.2
75
125
61
265
77
-20
7.9
85
130
60
311
89
-19
9.0
400 Cfm/Ton 75/62
95
136
59
357
101
-19
10.1
Table 64: ZQ05 Charging Table
Air Flow Indoor Db/Wb
Outdoor DB ° F
Suction P psig
Suction Temp. ° F
Liquid P psig
Liquid Temp. ° F
Delta T Db ° F
Compr. amps
75
128
57
277
82
-27
10.8
85
129
54
320
94
-28
12.3
300 Cfm/Ton 80/62
95
131
50
363
106
-28
13.8
75
132
64
277
81
-25
10.8
85
137
61
323
92
-24
12.4
300 Cfm/Ton 80/67
95
143
59
368
103
-23
13.9
75
137
70
278
80
-23
10.8
85
146
69
325
90
-21
12.4
300 Cfm/Ton 80/72
95
154
68
373
101
-18
14.0
75
121
50
271
83
-26
10.7
85
124
47
316
94
-26
12.2
300 Cfm/Ton 75/62
95
127
45
360
106
-26
13.7
75
132
63
280
80
-23
10.9
85
136
61
325
92
-23
12.4
400 Cfm/Ton 80/62
95
140
58
370
104
-23
14.0
75
136
66
283
80
-22
11.0
85
141
65
328
91
-21
12.5
400 Cfm/Ton 80/67
95
147
63
373
103
-20
14.0
75
140
69
286
79
-20
11.0
85
147
69
331
90
-19
12.5
400 Cfm/Ton 80/72
95
153
68
377
101
-17
14.0
75
127
57
276
81
-21
10.8
85
132
55
322
93
-21
12.3
400 Cfm/Ton 75/62
95
136
53
367
104
-21
13.9
INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A
84
Johnson Controls Ducted Systems
Summary of Contents for ZQ Series
Page 2: ...2 INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Page 88: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 88 Johnson Controls Ducted Systems ...
Page 89: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 89 Johnson Controls Ducted Systems ...
Page 90: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 90 Johnson Controls Ducted Systems ...
Page 91: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 91 Johnson Controls Ducted Systems ...