Gas Heat Unit Configuration
•
When W1 is energized FAN1, FAN2, and H1
outputs will energize, and the indoor fan VFD
will run at 100%. When W2 is energized, H2
output will energize.
Note:
A 30 second fan on delay will start once
the Gas Valve input (MV) is energized. If MV
input is energized without a call for heat (W1/
W2), Fan will enable.
Electric Heat Unit Configuration
•
When W1 is energized FAN1, FAN2, and H1
outputs will energize, and the indoor fan VFD
will run at 100%. When W2 is energized, H2
output will energize.
Table 40: Supply Fan Speed
Control Type
Fan Output
Single Stage Cool (Y1)
7.3-7.4VDC (67%),
10VDC (100%)
1
/>
Two Stage Cool (Y1,Y2)
7.3-7.4VDC (67%),
10 VDC (100%)
Single Stage Heat (W1)
10VDC (100%)
Two Stage Heat (W1,W2)
10VDC (100%)
Fan only
6 VDC (50%)
1
10VDC signal is provided with FAN2 output only when Y2 is
energized
VFD Operation
•
The VFD output is a 2-10VDC signal with a
minimum off time between fan cycles of 10
seconds, and a minimum on time for fan
cycles of 30 seconds.
Supply Fan Only Operation
•
The Fan is controlled by the G Thermostat
input, and has lowest priority for sequences
within the ETC board. When the G input is
energized with a call for fan on the ETC, 24VAC
will be applied to FAN1 output, and 6VDC will
be applied to VFD output to produce 50% fan
speed.
Table 41: Fault Codes
SR. No.
Condition
Red LED
Green LED
1
Power failure
Off
Off
2
Control Failure
ON
Off
3
Blackout condition
7 pulses
Off
4
Brownout condition
6 pulses
Off
5
Limit switch fault
8 pulses
Off
6
Dual HPS faults
3 pulses
3 pulses
7
HPS1 fault
Off
3 pulses
8
HPS2 fault
3 pulses
Off
9
Dual LPS faults
4 pulses
4 pulses
10
LPS1 fault
Off
4 pulses
11
LPS2 fault
4 pulses
Off
12
Dual FS fault
5 pulses
5 pulses
13
FS1 fault
Off
5 pulses
14
FS2 fault
5 pulses
Off
15
GV false proof
9 pulses
Off
16
GV lost proof
10 pulses
Off
17
2nd stage in
ASCD (heat/cool)
Rapid flash
On
18
2nd stage on
(heat/cool)
On
On
19
1st stage in
ASCD (heat/cool)
Off
Rapid flash
20
1st stage On
(heat/cool)
Off
On
21
Fan only (No
heat/cool)
Off
Fast heartbeat
22
No alarms
in memory
2 pulses
2 pulses
23
Normal idle
Off
Slow heartbeat
24
Factory test mode
Rapid flash
Rapid flash
Push Button
Hold down for:
•
0 to 2 seconds: 5 most recent error codes in
the history will flash on the LEDs
•
2 to 5 seconds: clear anti-short cycle timers
and reset any active lockouts
•
> 5 seconds: clear all fault history
INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A
56
Johnson Controls Ducted Systems
Summary of Contents for ZQ Series
Page 2: ...2 INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Page 88: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 88 Johnson Controls Ducted Systems ...
Page 89: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 89 Johnson Controls Ducted Systems ...
Page 90: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 90 Johnson Controls Ducted Systems ...
Page 91: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 91 Johnson Controls Ducted Systems ...