5. For gas heating models, you must move
the supply air temperature (SAT) sensor to
the working position to ensure proper SAT
readings. The SAT sensor is shipped in the
supply air compartment.
a. Move the SAT sensor to the inside of the
supply air duct. See item A in Figure 5.
b. Use the excess wire available to its full
length to drop or mount the SAT sensor in
the duct. Avoid close contact with the gas
heat exchanger.
c. Use the shipping bracket to hold the SAT
sensor in the supply air stream. See Figure
3 for the factory SAT sensor location and
Figure 5 for the sensor relocation.
Figure 3: Supply air temperature sensor
6. For units equipped with an economizer or
motorized OD air damper, you must move
the return air temperature (RAT) sensor to
the working position to ensure proper RAT
readings. See Item B in Figure 5
a. Move the RAT sensor to the inside of the
return air duct verifying that the sensor is
at least 6 in. below the unit duct opening.
The sensor must read the return air
temperature not mixed return air and
outdoor air temperatures.
b. Use the excess wire available to its full
length to drop or mount the RAT sensor in
the duct.
c. You can use the shipping bracket to hold
the RAT sensor in the return air stream.
See for the factory RAT sensor location
and Figure 5 for the sensor relocation.
Figure 4: Factory-mounted return air
temperature sensor
A
Filter rack and filters
B
RAT sensor
Figure 5: Supply and return air ducts
A
Supply air duct
B
Return air duct
7. If an optional return air smoke detector is
installed, you must move the return air sensor
from the factory-shipped position (upside
down) to the working position (right side up).
Then slide the flex tube over the stub and
INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A
10
Johnson Controls Ducted Systems
Summary of Contents for ZQ Series
Page 2: ...2 INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Page 88: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 88 Johnson Controls Ducted Systems ...
Page 89: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 89 Johnson Controls Ducted Systems ...
Page 90: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 90 Johnson Controls Ducted Systems ...
Page 91: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 91 Johnson Controls Ducted Systems ...