7. Review the RPM range for the motor options
available. Select the appropriate drive if
multiple drives are available for the chosen
motor.
8. Determine turns open to obtain the desired
operation point.
Example
1. 1600 CFM, bottom supply
2. 1.2 iwg
3. Using the airflow performance table below,
the following data point was located:
1359 RPM & 1.11 BHP.
4. Using the RPM selection table below, Model
ZQ and Size 05 (4 tons) is found.
5. 1359 RPM is within the range of the 2.4 HP,
High Static drives.
6. Using the 2.4 HP motor and High Static drive,
2-1/2 turns open will achieve 1359 RPM.
Airflow Performance
Example Supply Air Blower Performance
Table 22: ZQ05 (4.0 Ton) Bottom Duct
1
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1200
908
0.34
994
0.45
1072
0.55
1145
0.64
1214
0.74
1283
0.83
1352
0.92
1424
1.01
1502
1.11
1586
1.20
1300
921
0.40
1007
0.51
1085
0.61
1158
0.70
1227
0.80
1296
0.89
1365
0.98
1437
1.07
1514
1.17
1599
1.26
1400
938
0.47
1023
0.58
1101
0.68
1174
0.77
1244
0.86
1312
0.96
1382
1.05
1454
1.14
1531
1.23
1616
1.33
1500
959
0.55
1044
0.65
1122
0.75
1195
0.85
1265
0.94
1333
1.03
1403
1.12
1475
1.21
1552
1.31
1637
1.41
1600
985
0.63
1070
0.73
1148
0.83
1221
0.93
1290
1.02
1359
1.11
1428
1.20
1500
1.29
1578
1.39
--
--
1700
1015
0.71
1100
0.82
1179
0.92
1251
1.01
1321
1.11
1389
1.20
1459
1.29
1531
1.38
1608
1.48
--
--
1800
1050
0.81
1136
0.91
1214
1.01
1287
1.11
1356
1.20
1425
1.29
1494
1.39
1566
1.48
1644
1.57
--
--
1900
1091
0.91
1176
1.02
1254
1.12
1327
1.21
1397
1.31
1465
1.40
1534
1.49
1607
1.58
--
--
--
--
2000
1136
1.02
1222
1.13
1300
1.23
1372
1.32
1442
1.42
1510
1.51
1580
1.60
--
--
--
--
--
--
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 2.4-hp
Field supplied AK41 x 3/4" fixed blower pulley with Motor rated at 2.4-hp
--
Exceeds recommended blower speed
1
Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
Note:
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP. kW = 0.929
x BHP
Table 23: Example RPM Selection
Model
Size (Tons)
Airflow
Option
Phase
Max BHP
Blower
Sheave
Motor
Sheave
6 Turns
Open
5 Turns
Open
4 Turns
Open
3 Turns
Open
2 Turns
Open
1 Turns
Open
Fully
Closed
Std.
Direct Drive
Med.
1
1.5
AK46
1VL34
N/A
792
875
958
1042
1125
1208
Med.
3
2.4
AK46
1VL34
N/A
792
875
958
1042
1125
1208
ZQ
05 (4)
H. Static
3
2.4
AK46
1VL44
N/A
1167
1250
1333
1417
1500
1593
Table 24: Example Additional Static Resistance
Electric Heat kW
2
Model
Size Tons
CFM
Cooling Only
1
Economizer
2,3
4” Filter
2
6/6.5
9.2/10.5/11
13.8/14/16
23
1200
0.07
0.06
---
0.01
0.01
0.02
0.03
1300
0.10
0.07
---
0.01
0.01
0.03
0.03
1400
0.12
0.08
---
0.02
0.02
0.03
0.04
1500
0.14
0.08
---
0.02
0.02
0.04
0.04
1600
0.16
0.09
---
0.02
0.02
0.04
0.05
1700
0.18
0.10
---
0.03
0.03
0.05
0.05
1800
0.22
0.11
---
0.03
0.03
0.05
0.06
1900
0.25
0.12
---
0.04
0.04
0.06
0.07
ZQ
05 (4.0)
2000
0.28
0.13
---
0.04
0.04
0.07
0.08
INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A
46
Johnson Controls Ducted Systems
Summary of Contents for ZQ Series
Page 2: ...2 INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Page 88: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 88 Johnson Controls Ducted Systems ...
Page 89: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 89 Johnson Controls Ducted Systems ...
Page 90: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 90 Johnson Controls Ducted Systems ...
Page 91: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 91 Johnson Controls Ducted Systems ...