Power Supply T
erminal Connections (Option /TB, /A2TB, and /REK)
8.2 Power Supply and Ground Wiring
(1) All cable ends must be furnished with crimp-on type solderless lugs (for 4 mm screws).
(2) Examples of applicable cables:
Cross-sectional area of the cable conductor:
2.0 mm
2
. *
For the power supply, use cable having a cross-sectional area of at least 1.25 mm
2
.
Applicable cable:
600 V vinyle insulated cable (IV) stranded wires, conforming to JIS
C3307.
PVC insulated cables for electric appliances (KIV) stranded wires,
conforming to JIS C3316.
Note *: Power supply cables should be determined from the instrument power
consumption-they must have conductors with cross-sectional area of at least
1.25
mm
2
.
(3) Wirings to power supply and ground terminals should be made after completion of signal
terminal wirings.
(When signal terminal wirings are made after completion of power supply wiring, pull the
internal unit approximately half way out of the housing. Do not remove the power terminal
block.)
(4) After completing the power supply and ground wiring, mount the power terminal cover.