5-13
IM 01B04K02-02E
Setting
1
2
3
App
1
2
3
5
6
7
8
4
No.
Parameter Name
Symbol
Description
Setting Range Factory-set
Value
Display
Conditions
E
Setting Alarm
Parameters
SET(ALM)
E01
Alarm 1 Set Point
SET POINT1 Sets alarm 1 set point in
engineering
unit.
Note: Initialized when
- SENSOR TYPE1
- TC TYPE1
- RTD TYPE1
- UNIT1
- INPUT1 H_RNG
- INPUT1 L_RNG
- SCH1 or SCL1 is
changed.
Default: Maximum value
of measuring input range
when ALM1 ACTION =
DIRECT.
Minimum value of
measuring input range
when ALM1 ACTION =
REVERSE.
-19999 to 32000
(engineering unit)
(Note)
Displayed on all
E02
Alarm 2 Set Point
SET POINT2 Sets alarm 2 set point in
engineering unit.
Note: Initialized when
- SENSOR TYPE1
- TC TYPE1
- RTD TYPE1
- UNIT1
- INPUT1 H_RNG
- INPUT1 L_RNG
- SCH1 or SCL1 is
changed.
Default: Maximum value
of measuring input range
when ALM2 ACTION =
DIRECT.
Minimum value of
measuring input range
when ALM2 ACTION =
REVERSE.
-19999 to 32000
(engineering unit)
(Note)
Displayed on
SALD-724.
E07
Alarm 1 Action
ALM1 ACTION Displays the direction
(direct/reverse) of action of
alarm 1.
The setting can be changed
on the SALD-xx0.
On the SALD-xx4, displays
the state of the jumpers on
the main board.
DIRECT
REVERSE
DIRECT
Displayed on all
E08
Alarm 2 Action
ALM2 ACTION Displays the direction
(direct/reverse) of action of
alarm 2.
The setting can be changed
on SALD-xx0.
On the SALD-xx4, displays
the state of the jumpers on
the main board.
DIRECT
REVERSE
REVERSE
Displayed on
SALD-724.
5.4 Parameter List