5-11
IM 01B04K02-02E
Setting
1
2
3
App
1
2
3
5
6
7
8
4
No.
Parameter Name
Symbol
Description
Setting Range
Factory-set
Value
Display
Conditions
D
Setting Parameters SET(I/O)
D01
Tag Number 1
TAG NO.1
8 alphanumerics can be
entered.
Displayed on all
D02
Tag Number 2
TAG NO.2
8 alphanumerics can be
entered.
D03
Comment 1
COMMENT1 8 alphanumerics can be
entered.
D04
Comment 2
COMMENT2 8 alphanumerics can be
entered.
D07
Sensor Type 1
SENSOR
TYPE1
Selects the sensor type of
universal input.
TC
mV
RTD
Item to be
specified at
ordering.(*1)
Displayed on
SALD-7xx
D08
Thermocouple
Type 1
TC TYPE1
Selects the thermocouple
type when universal input
and TC.
Note: Initialized when
SENSOR TYPE1 is
changed.
Type K
Type E
Type J
Type T
Type R
Type S
Type B
Type N
Type W3
Type W5
Item to be
specified at
ordering.
Displayed on
SALD-7xx, and
when SENSOR
TYPE1=TC.
D09
RTD Type 1
RTD TYPE1
Selects the RTD type when
universal input and RTD.
Note: Initialized when
SENSOR TYPE1 is
changed.
Pt100-90
Pt100-68
JPt100
Pt50
Item to be
specified at
ordering. (*2)
Displayed on
SALD-7xx and
when SENSOR
TYPE1=RTD.
D15
Input 1 Unit
UNIT1
Selects the unit when
temperature input.
degC
K
degF
degC
degF
(when /FCAL
is specified.)
Displayed on
SALD-2xx, SALD-
3xx, or SALD-7xx
(universal input)
and when
SENSOR
TYPE1=TC or
RTD.
D27
Input 1 LOW Range INPUT1 L_
RNG
Settable at mV input only.
Sets the minimum value of
input range.
Note: Initialized when
- SENSOR TYPE 1
- TC TYPE1
- RTD TYPE1 or
- UNIT1 is changed.
-50.0 to 150.0 mV
However, INPUT1
L_RNG<H_RNG
0.0 mV
Displayed on
SALD-1xx or
SALD-7xx
(universal
input) and
when SENSOR
TYPE1=mV.
D28
Input 1 HIGH Range INPUT1 H_
RNG
Settable at mV input only.
Sets the maximum value of
input range.
Note: Initialized when
- SENSOR TYPE1
- TC TYPE1
- RTD TYPE1
- UNIT1 is changed.
-50.0 to 150.0 mV
However, INPUT1
L_RNG<H_RNG
100.0 mV
D31
Burnout1
BURN OUT1 Selects the action of input 1
burnout.
For SALD-xx0, the setting
is changeable.
For SALD-xx4, indicates
the status of setting jumper
on main board.
OFF
UP
DOWN
Item to be
specified
at ordering.
(optional)
If not specified,
the burnout
(B31) is set to
OFF.
Displayed on all
D37
ON/OFF of Input
Reference Junction
Compensation
RJC
Sets ON/OFF for reference
junction compensation.
For SALD-xx0, the setting
is changeable.
For SALD-xx4, indicates
the status of setting jumper
on main board.
ON
OFF
ON
Displayed on
SALD-2xx or
SALD-7xx
(universal
input) and
when SENSOR
TYPE1=TC
*1: Optional for SALD-7xx. If not specified, Sensor Type 1(D07) is set to RTD.
*2: Optional for SALD-7xx. If not specified, RTD Type 1(D09) is set to Pt100 (ITS-90).
5.4 Parameter List