5.2 Setting Jumper
The SALD is provided with the following jumpers.
Jumper Code
Jumper Name
SALD-xx0
SALD-xx4
RJC
RJC (reference junction
compensation) jumper
Not available
Available
W.P.
Parameter Write Protect jumper
Available
Available
BURN OUT(UP)
Burnout action setting jumper
Not available
Available
BURN OUT(DOWN)
ALM1
Alarm 1 action setting jumper
Not available
Available
ALM2
Alarm 2 action setting jumper
(SALD-724 only)
Not available
Available
• Parameter Write Protect jumper
When this jumper is set to ON, changing of parameters by the key switches and Handy
Terminal is disabled. “LOC” will be displayed on the display setter if the “→” switch is
pressed with the SP1 or SP2 parameter displayed on the display setter.
To cancel the “LOC” display and return to the previous display, press any key.
• RJC (reference junction compensation) jumper
Setting is required only for thermocouple input.
When set to ON, the reference junction compensation action is activated.
• Alarm action setting jumper
This jumper is for setting the direction of alarm action.
The table below shows the relationship between direction of alarm action and direction of
relay action.
Direction of alarm relay action: De-energized at normal operation (Factory-shipped settings)
ALMn
Direction of alarm action
Input value < Set point
Set point < Input value
DIR
Direct (high-limit alarm)
Output relay de-energized
Output relay energized
RVS
Reverse (low-limit alarm)
Output relay energized
Output relay de-energized
Direction of alarm relay action: Energized at normal operation
ALMn
Direction of alarm action
Input value < Set point
Set point < Input value
DIR
Direct (high-limit alarm)
Output relay energized
Output relay de-energized
RVS
Reverse (low-limit alarm)
Output relay de-energized
Output relay energized
Factory-shipped settings : ALM1 DIR, ALM2 RVS
• Burnout action setting jumper
BURN OUT Setting
Burnout OFF
Set both of UP and DOWN to OFF.
Upscale
Set only UP to ON.
Downscale
Set only DOWN to ON.
Do not set both UP and DOWN to ON. The action is not guaranteed.