4. Appendix
4-4
TI 30A10A05-01E
4.4
Time Synchronization
Vnet/IP synchronizes the time between the Vnet/IP stations connected to a Vnet/IP
network.
n
Types of clock time
A Vnet/IP station has the following types of clock time:
• System time:
Managed by the Vnet/IP station system software.
• Network time:
Clock time retained by the Vnet/IP station hardware. It is synchronized as
the standard time following the time master.
n
Time accuracy of a Vnet/IP station
The time synchronization process standardizes the network time for all Vnet/IP stations
connected to the Vnet/IP network.
Furthermore, the system software for Vnet/IP stations updates its system time to match the
network time. The following table describes the deviation between the network time and system
time in Vnet/IP stations.
Table Accuracy of the system time
Vnet/IP stations
Error from network time
Time adjustment method
HIS, ENG, SENG
Max. 0.5 sec
The deviation between the network time and
system time is checked. If there is a deviation
of 0.5 seconds or more, the system time is
adjusted to match the network time.
FCS, SCS, and V net router
None
The system time always synchronizes with the
network time.
Aug.19,2011-00
Summary of Contents for Vnet/IP
Page 2: ...Blank Page...
Page 8: ...Blank Page...