2. Vnet/IP Network Configuration
2-14
TI 30A10A05-01E
Dec. 26, 2016-00
2.2.4
Connecting network switches by Ring Topology
n
Configuring a network using Ring Topology
A ring network can be configured by connecting multiple L2SWs in a loop in a Vnet/IP domain.
A system configuration where Vnet/IP network is configured in a ring network is as shown below.
(1) Setting Ring protocol
Ring protocol has to be set to both Bus 1 and Bus 2 of the network switch for Vnet/IP to
make both of the Bus 1 and Bus 2 have ring configuration.
(2) Acknowledgment of occurrence of and recover from failures
The system has to be engineered to generate alarms when ring failures occur as well as
recover from failures. Specifically, a signal from a FAULT output terminal of the network
switch assigned as the Ring manager (RM) has to be received by a digital input module of
CENTUM VP’s FCS, and its on/off is to be notified to an HIS.
(3) Identifying failed point
Identification of the failed point in the ring network is done by the network management
system (PMS) in a computer independent from HIS or by manually.
When configuring a ring network, the network has to be segregated by VLAN for security
and prioritize traffics.
F020208E.ai
HIS
FCS
FCS
FCS
: Bus 1
: Bus 2
HIS
HIS/ENG
Computer for
ring management
L2SW
L2SW
L2SW
FAULT Signal
(2) Acknowledgment of
occurrence of and
recovery from failure
Setting Ring protocol
Identifying the failed point
(3)
Figure Ring Network Structure
Contact Yokogawa for more details about how to configure a network using Ring topology.