UTAdvanced UP55A
Program Pattern Setup Charts
CAUTION
You can register max. 99 program segments with the UP55A controller. Create as many copies of the chart as necessary.
System name
Maximum value of PV input range / Maximum value of PV input scale (250.0)
Program No.
Unit (°C)
Program name
Model
Serial No.
A program pattern can be drawn in the right table.
Minimum value of PV input range / Minimum value of PV input scale (0.0)
Parameter symbol
User settings
Parameter symbol
Parameter name
TMU
HH.MM
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
SEG.T
TIME
TSP
Final target setpoint
100.0
100.0
200.0
200.0
50.0
50.0
ZON
0
TSP
Final target setpoint for Program pattern-2 retransmission
PT2.G
OFF
TIME
Segment time setting
0.50
0.30
1.00
0.30
0.50
0.30
TM.RT
Segment ramp-rate setting
S.PID
Segment PID number selection
1
2
3
4
5
6
JC
Junction code
CONT
CONT
CONT
CONT
CONT
CONT
PV.TY1
PV event-1 type
5
1
5
1
6
2
PV.EV1
PV event-1 setpoint
5.0
110.0
5.0
210.0
5.0
10.0
Parameter symbol
User settings
PV.TY2
PV event-2 type
SSP
50.0
PV.EV2
PV event-2 setpoint
SSP
PV.TY3
PV event-3 type
STC
SSP
PV.EV3
PV event-3 setpoint
WT.SW1
PV.TY4
PV event-4 type
WZ.UP1
PV.EV4
PV event-4 setpoint
WZ.LO1
PV.TY5
PV event-5 type
WT.TM1
PV.EV5
PV event-5 setpoint
WT.SW2
PV.TY6
PV event-6 type
WZ.UP2
PV.EV6
PV event-6 setpoint
WZ.LO2
PV.TY7
PV event-7 type
WT.TM2
PV.EV7
PV event-7 setpoint
WT.SW3
PV.TY8
PV event-8 type
WZ.UP3
PV.EV8
PV event-8 setpoint
WZ.LO3
TME1
Start condition of time event 1
OFF
OFF
ON
OFF
ON
OFF
WT.TM3
T.ON1
On time of time event 1
0.25
WT.SW4
T.OF1
Off time of time event 1
0.20
0.20
WZ.UP4
TME2
Start condition of time event 2
OFF
ON
OFF
ON
OFF
ON
WZ.LO4
T.ON2
On time of time event 2
WT.TM4
T.OF2
Off time of time event 2
WT.SW5
TME3
Start condition of time event 3
WZ.UP5
T.ON3
On time of time event 3
WZ.LO5
T.OF3
Off time of time event 3
WT.TM5
TME4
Start condition of time event 4
R.CYCL
T.ON4
On time of time event 4
R.STRT
T.OF4
Off time of time event 4
R.END
TME5
Start condition of time event 5
T.ON5
On time of time event 5
T.OF5
Off time of time event 5
TME6
Start condition of time event 6
T.ON6
On time of time event 6
T.OF6
Off time of time event 6
TME7
Start condition of time event 7
T.ON7
On time of time event 7
T.OF7
Off time of time event 7
TME8
Start condition of time event 8
T.ON8
On time of time event 8
T.OF8
Off time of time event 8
TME9
Start condition of time event 9
T.ON9
On time of time event 9
T.OF9
Off time of time event 9
TME10
Start condition of time event 10
T.ON10
On time of time event 10
T.OF10
Off time of time event 10
TME11
Start condition of time event 11
T.ON11
On time of time event 11
T.OF11
Off time of time event 11
TME12
Start condition of time event 12
T.ON12
On time of time event 12
T.OF12
Off time of time event 12
TME13
Start condition of time event 13
T.ON13
On time of time event 13
T.OF13
Off time of time event 13
TME14
Start condition of time event 14
T.ON14
On time of time event 14
T.OF14
Off time of time event 14
TME15
Start condition of time event 15
T.ON15
On time of time event 15
T.OF15
Off time of time event 15
TME16
Start condition of time event 16
T.ON16
On time of time event 16
T.OF16
Off time of time event 16
The following parameters are common parameters for the program pattern
specified.
*******
*******
*******
Program time unit
Segment setting method
Zone PID selection
UP55A
Parameter name
The following parameters are necessary to be set before programming.
Note that the program is deleted if TMU or SEG.T is changed after creating
programs.
Lower-side wait zone 1
Wait time 1
Parameter name
Starting target setpoint
Starting target setpoint (for program pattern-2 retransmission)
Start code
Upper-side wait zone 5
Wait function ON/OFF 4
Upper-side wait zone 4
Lower-side wait zone 4
Wait time 4
Upper-side wait zone 2
Segments
Program pattern-2 retransmission
Wait function ON/OFF 5
Wait function ON/OFF 3
Upper-side wait zone 3
Lower-side wait zone 2
Wait time 2
Wait function ON/OFF 1
Upper-side wait zone 1
Note that the program patterns are all deleted if the settings change after creating program patterns.
Be sure to check the PV input range, Program time unit (TMU), and Segment setting method (SEG.T) before creating.
Repeat cycle end segment number
Number of repeat cycles
Repeat cycle start segment number
Lower-side wait zone 5
Wait time 5
Lower-side wait zone 3
Wait time 3
Wait function ON/OFF 2
The programming example given here demonstrates how to do the tasks outlined below.
1) Program the controller to start program operation at 50.0°C and raise the temperature up to 100.0°C in 50 minutes.
2) When the temperature reaches 100.0°C, keep it at this level for 30 minutes.
3) Raise the temperature up to 200.0°C in 60 minutes.
4) When the temperature reaches 200.0°C, keep it at this level for 30 minutes.
5) Lower the temperature to 50.0°C in 50 minutes.
6) When the temperature reaches 50.0°C, keep it at this level for 30 minutes.
PV input ranges are following:
Maximum value of PV input range: 250.0°C
Minimum value of PV input range: 0.0°C
PV input unit: C
Zone PID selection (ZON): Segment PID selection (0)
Segment setting method (SEG.T): Segment time setting (TIME)
Program time unit (TMU): hour.minute (HH.MM)