YOKOGAWA UTAdvanced UP55A Technical Information Download Page 22

DI Function Numbering

Menu

Symbol

Name

Display level

Setting range

Initial value

User setting

DI.NU

PT.B0

Bit-0 of Program pattern number

EASY

5089

PT.B1

Bit-1 of Program pattern number

EASY

5090

PT.B2

Bit-2 of Program pattern number

EASY

5091

PT.B3

Bit-3 of Program pattern number

EASY

5092

PT.B4

Bit-4 of Program pattern number

EASY

5093

PT.B5

Bit-5 of Program pattern number

EASY

OFF

PN.B0

Bit-0 of PID number

STD

OFF

PN.B1

Bit-1 of PID number

STD

OFF

PN.B2

Bit-2 of PID number

STD

OFF

PN.B3

Bit-3 of PID number

STD

OFF

MP.B0

Bit-0 of manual preset output number

STD

OFF

MP.B1

Bit-1 of manual preset output number

STD

OFF

MP.B2

Bit-2 of manual preset output number

STD

OFF

PT.BC

Bit changing method of program pattern
number

PRO

0: Status switch 1
1: Status switch 2
2: BCD switch

0

PN.BC

Bit changing method of PID number

PRO

0

MP.BC

Bit changing method of manual preset output
number

PRO

0

DI1-DI3 Contact Type Setting

Menu

Symbol

Name

Display level

Setting range

Initial value

User setting

DI.D

DI1.D

DI1 contact type

PRO

0

DI2.D

DI2 contact type

PRO

0

DI3.D

DI3 contact type

PRO

0

DI Setting

(E1 terminal area)

(DI11-DI15)

(E2 terminal area)

(DI21-DI25)

(E3 terminal area)

(DI31-DI35)

(E4 terminal area)

(DI41-DI45)

Menu

Symbol

Name

Display level

Setting range

Initial value

User setting

User setting

User setting

User setting

DI.D

DI1.D

DIn1 contact type

PRO

0

DI2.D

DIn2 contact type

PRO

0

DI3.D

DIn3 contact type

PRO

0

DI4.D

DIn4 contact type

PRO

0

DI5.D

DIn5 contact type

PRO

0

n: Terminal area number (1 to 4)

AL1-AL3 Function Registration

Menu

Symbol

Name

Display level

Setting range

Initial value

User setting

ALM

AL1.S

AL1 function selection

STD

4801

AL2.S

AL2 function selection

STD

4802

AL3.S

AL3 function selection

STD

4803

OR.S

OUT relay function selection

STD

OFF

OR2.S

OUT2 relay function selection

STD

OFF

AL1.D

AL1 contact type

PRO

0

AL2.D

AL2 contact type

PRO

0

AL3.D

AL3 contact type

PRO

0

OR.D

OUT relay contact type

PRO

0

OR2.D

OUT2 relay contact type

PRO

0

DO Setting

(E1 terminal area)

(DO11-DO15)

(E2 terminal area)

(DO21-DO25)

(E3 terminal area)

(DO31-DO35)

(E4 terminal area)

(DO41-DO45)

Menu

Symbol

Name

Display level

Setting range

Initial value

User setting

User setting

User setting

User setting

DO

DO1.S

DOn1 function selection

STD

See left

DO2.S

DOn2 function selection

STD

See left

DO3.S

DOn3 function selection

STD

See left

DO4.S

DOn4 function selection

STD

See left

DO5.S

DOn5 function selection

STD

See left

DO1.D

DOn1 contact type

PRO

0

DO2.D

DOn2 contact type

PRO

0

DO3.D

DOn3 contact type

PRO

0

DO4.D

DOn4 contact type

PRO

0

DO5.D

DOn5 contact type

PRO

0

n: Terminal area number (1 to 4)

I/O Display

Menu

Symbol

Name

Display level

Setting range

I/O

KEY

Key status

PRO

X000

DI1-DI3 status (equipped as standard)

PRO

X100

DI11-DI16 status (E1-terminal area)

PRO

X200

DI21-DI26 status (E2-terminal area)

PRO

X300

DI31-DI35 status (E3-terminal area)

PRO

X400

DI41-DI46 status (E4-terminal area)

PRO

Y000

AL1-AL3 status (equipped as standard)

PRO

Y100

DO11-DO15 status (E1-terminal area)

PRO

Y200

DO21-DO25 status (E2-terminal area)

PRO

Y300

DO31-DO35 status (E3-terminal area)

PRO

Y400

DO41-DO45 status (E4-terminal area)

PRO

System Setting

Menu

Symbol

Name

Display level

Setting range

Initial value

User setting

SYS

R.MD

Restart mode

STD

CONT: Continue action set before power failure.
MAN: Start from MAN.
RESET: Start from AUTO and RESET. The preset output value is outputted.
* Set how the controller should recover from a power failure of 5 seconds or
more.

CONT

R.TM

Restart timer

STD

0 to 10 s
* Set time between power on and the instant where controller starts
computation.

0

EPO

Input error preset output

STD

0: Preset output
1: 0% output
2: 100% output
* Set preset output value when the input burnout or ADC error occurs. Manual
output is prioritized when the input burnout occurs in MAN.

0

C.GRN

Response as GREEN Series

PRO

OFF: Works as UP55A in communication of device information response or
broadcasting.
ON: Works as GREEN Series in communication of device information response
or broadcasting.

OFF

FREQ

Power frequency

EASY

AUTO, 60: 60 Hz, 50: 50 Hz

AUTO

QSM

Quick setting mode

EASY

OFF: Disable
ON: Enable

ON

LANG

Guide display language

EASY

ENG: English
FRA: French
GER: German
SPA: Spanish

Depends on the Model and
Suffix Codes

PASS

Password setting

EASY

0 (No password) to 65535
Once a password is set, you can no longer choose not to set a password.

0

SMEC

Sampling period error counter

PRO

0 to 65535 (display only)

0 when power is turned on.

Initialization

Menu

Symbol

Name

Display level

Setting range

Initial value

User setting

INIT

U.DEF

Initialization to user default value

PRO

12345: Initialization, automatically returned to "0" after initialization.

0

F.DEF

Initialization to factory default value

PRO

-12345: Initialization, automatically returned to "0" after initialization.

0

P.DEF

Clearing all program pattern data

PRO

13579: Initialization, automatically returned to "0" after initialization.
* Data all deletions in menu [PROG]

0

Set an I relay number of contact input.
Set “OFF” to disable the function.

Standard terminals
 DI1: 5025, DI2: 5026, DI3: 5027
E1-terminal area
 DI11: 5041, DI12: 5042, DI13: 5043, DI14: 5044, DI15: 5045, DI16: 5046
E2 -terminal area
 DI21: 5057, DI22: 5058, DI23: 5059, DI24: 5060, DI25: 5061, DI26: 5062
E3-terminal area
 DI31: 5073, DI32: 5074, DI33: 5075, DI34: 5076, DI35: 5077
E4-terminal area
 DI41: 5089, DI42: 5090, DI43: 5091, DI44: 5092, DI45: 5093, DI46: 5094

0: Status switch 1
1: Status switch 2

0: The assigned function is enabled when the contact input is closed.
1: The assigned function is enabled when the contact input is opened.

0: The assigned function is enabled when the contact input is closed.
1: The assigned function is enabled when the contact input is opened.

Set an I relay number.
Setting range: 4001 to 6304
No function: OFF
PV event 1: 4801, PV event 2: 4802,
PV event 3: 4803, PV event 4: 4805,
PV event 5: 4806, PV event 6: 4807,
PV event 7: 4809, PV event 8: 4810,
Time event 1: 4817, Time event 2: 4818,
Time event 3: 4819, Time event 4: 4821,
Time event 5: 4822, Time event 6: 4823,
Time event 7: 4825, Time event 8: 4826,
Time event 9: 4833, Time event 10: 4834,
Time event 11: 4835, Time event 12: 4837,
Time event 13: 4838, Time event 14: 4839,
Time event 15: 4841, Time event 16: 4842,
Alarm 1: 4353, Alarm 2: 4354, Alarm 3: 4355, Alarm 4: 4357,
Alarm 5: 4358, Alarm 6: 4359, Alarm 7: 4361, Alarm 8: 4362,
AUTO (ON ) / MAN (OFF) status: 4177,
Program RESET status: 4181, Program RUN status: 4182,
Local operation status: 4183,
Remote operation status: 4185,
HOLD mode status: 4189,
Program advance status: 4187,
Pattern end signal (1 second): 4265,
Pattern end signal (3 seconds): 4266,
Pattern end signal (5 seconds): 4267,
Wait end signal (1 second) : 4257,
Wait end signal (3 seconds) : 4258,
Wait end signal (5 seconds) : 4259,
Output tracking (ON) switching signal: 4186,
FAIL (Normally ON) output: 4256

Read only
See User's Manual.

0: When the event of assigned function occurs, the contact output is closed.
1: When the event of assigned function occurs, the contact output is opened.

0: When the event of assigned function occurs, the contact output is closed.
1: When the event of assigned function occurs, the contact output is opened.

Same as AL1.S.

DO11=4805, DO12=4806, DO13=4807, DO14=4809, DO15=4810,
DO21=4817, DO22=4818, DO23=4819, DO24=4821, DO25=4822,
DO31=4823, DO32=4825, DO33=4826, DO34=4833, DO35=4834,
DO41=OFF, DO42=OFF, DO43=OFF, DO44=OFF, DO45=OFF

0: When the event of assigned function occurs, the contact output is closed.
1: When the event of assigned function occurs, the contact output is opened.

Page 22 / 25

Summary of Contents for UTAdvanced UP55A

Page 1: ...UTAdvanced UP55A Program Controller Parameter Maps and Lists TI 05P02C41 01EN Copyright July 2011 1st Edition July 2011 Page 1 25...

Page 2: ...eet describes the setting range and initial value of operation parameters and setup parameters There is a column for user settings Program Data Sheet This sheet can be used for recording the setting v...

Page 3: ...inal area E1 to E4 in the Parameter Setting Display Displays a parameter symbol Displays the setting conditions of the parameter display level function Parameter display level EASY PRO Easy setting mo...

Page 4: ...t is blinking to move between digits according to the parameter Description Used to switch the Operation Displays Press the key in the Operation Display to switch the provided Operation Displays Press...

Page 5: ...parameter and operation status Parameter Display Transition and Setup Operation To move to the Operation Parameter Setting Display To move to the Setup Parameter Setting Display To move to the Operati...

Page 6: ...he Up or Down arrow key to change the setpoint 6 Press the SET ENTER key to register the setpoint the setpoint stops blinking This completes the setting procedure How to Cancel Parameter Setting To ca...

Page 7: ...How to Set Parameter Setpoint Numeric Value Setting Selection Data Setting Time minute second Setting Page 7 25...

Page 8: ...14 segments Alphabet Symbol display and Data display 11 segments Alphabet Group display 7 segments Alphabet PV display 14 segments Symbol The following shows the parameter symbols menu symbols alphanu...

Page 9: ...CYCL 1 T ON16 99 T ON16 VT7 R STRT 1 T OF16 99 T OF16 VT8 R END END END HY1 END HY2 HY3 HY4 HY5 HY6 HY7 Symbol Corresponding parameters are displayedin all modes HY8 1 PYS1 2 PYS2 3 PYS3 4 PYS4 END MO...

Page 10: ...unction Numbering DI1 DI3 Contact Type Setting DI Setting E1 terminal area DI Setting E2 terminal area DI Setting E3 terminal area DI Setting E4 terminal area AL1 AL3 Function Registration DO Setting...

Page 11: ...Data Sheet WT SW1 Wait function ON OFF 1 STD OFF Disable ON Enable OFF See Sheet Program Data Sheet WZ UP1 Upper side wait zone 1 STD 0 5 of PV input range See Sheet Program Data Sheet WZ LO1 Lower s...

Page 12: ...ern 2 retransmission PT2 G ON Menu Symbol Name Display level Setting range Initial value User setting User setting LOC LSP Local target setpoint EASY 0 0 to 100 0 of PV input range EU Setting range P...

Page 13: ...hysteresis EASY 10 HY4 Alarm 4 hysteresis EASY 10 HY5 Alarm 5 hysteresis EASY 10 HY6 Alarm 6 hysteresis EASY 10 HY7 Alarm 7 hysteresis EASY 10 HY8 Alarm 8 hysteresis EASY 10 DYN1 Alarm 1 On delay time...

Page 14: ...haracteristic changes compared with response mode 3 Hunting suppressing function response mode Enables quick follow up and short converging time of PV for the changed SP 4 Overshoot suppressing functi...

Page 15: ...segment linearizer 3 output 2 PRO 0 0 A3 10 segment linearizer 3 input 3 PRO 0 0 B3 10 segment linearizer 3 output 3 PRO 0 0 A4 10 segment linearizer 3 input 4 PRO 0 0 B4 10 segment linearizer 3 outp...

Page 16: ...of PV input scale EASY Depends on the input type SL Minimum value of PV input scale EASY Depends on the input type BSL PV input burnout action STD OFF Disable UP Upscale DOWN Downscale Depends on the...

Page 17: ...SH Maximum value of AIN4 aux analog input scale EASY Depends on the input type SL Minimum value of AIN4 aux analog input scale EASY Depends on the input type BSL AIN4 aux analog input burnout action S...

Page 18: ...UT current output range STD 4 20 OU2 A OUT2 current output range STD 4 20 RET A RET current output range STD 4 20 Heater Break Alarm Setting Menu Symbol Name Display level Setting range Initial value...

Page 19: ...10M 10 minutes 30M 30 minutes 60M 60 minutes OFF When each parameter is displayed the terminal area E3 is displayed on Group display DeviceNet Communication Setting Menu Symbol Name Display level Set...

Page 20: ...when there has been no keystroke operation for 5 minutes OFF ON ON MLSD Least significant digital mask of PV display STD OFF With least significant digit ON Without least significant digit OFF Set a d...

Page 21: ...FF INIT INIT menu lock PRO OFF VER VER menu lock PRO OFF LVL LVL menu lock PRO OFF MODE MODE menu lock PRO OFF CS CS menu lock PRO OFF PROG PROG menu lock PRO OFF LOC LOC menu lock PRO OFF EDIT EDIT m...

Page 22: ...et output STD 0 Preset output 1 0 output 2 100 output Set preset output value when the input burnout or ADC error occurs Manual output is prioritized when the input burnout occurs in MAN 0 C GRN Respo...

Page 23: ...3 ECU 3 version EASY ECU4 ECU 4 version EASY PARA Parameter version EASY H VER Product version EASY SER1 Serial number 1 EASY SER2 Serial number 2 EASY MAC1 MAC address 1 EASY MAC2 MAC address 2 EASY...

Page 24: ...T ON7 On time of time event 7 T OF7 Off time of time event 7 TME8 Start condition of time event 8 T ON8 On time of time event 8 T OF8 Off time of time event 8 TME9 Start condition of time event 9 T O...

Page 25: ...on of time event 10 T ON10 On time of time event 10 T OF10 Off time of time event 10 TME11 Start condition of time event 11 T ON11 On time of time event 11 T OF11 Off time of time event 11 TME12 Start...