Program Pattern Setting
Program pattern-2
retransmission
(PT2.G=ON)
Menu
Symbol
Name
Display level
Setting range
Initial value
User setting
User setting
PROG>
PTNO.
TSP
Final target setpoint
EASY
0.0 to 100.0% of PV input range (EU)
(Setting range: P.RL to P.RH)
P.RL
See
Sheet"Program
Data Sheet"
See
Sheet"Program
Data Sheet"
TIME
Segment time setting
EASY
-: Unregistered
0.00 to 999.59 (“hour.minute” or “minute.second”)
* Setting available for the parameter SEG.T=TIME.
* Use the parameter TMU to set the time unit. (Common in the instrument.)
* If the setting is 0.00, TSP changes in stepwise after one control period.
-
See
Sheet"Program
Data Sheet"
TM.RT
Segment ramp-rate setting
EASY
-: Unregistered
Ramp: 0.0 to 100.0% of PV input range span (EUS) / 1 hour or 1 minute
Soak: 0.00 to 999.59 (“hour.minute” or “minute.second”)
* Setting available for the parameter SEG.T=TM.RT.
* Use the parameter TMU to set the time unit. (Common in the instrument.)
Per 1 hour: TMU=HH.MM,
Per 1 minute: TMU=MM.SS
* If it is set to 0.0% of the input range span, or the segment time 0.00, the
program moves to the next segment after one control period.
-
See
Sheet"Program
Data Sheet"
S.PID
Segment PID number selection
EASY
1 to 8
* PID number can be set when the parameter “ZON = 0.”
1
See
Sheet"Program
Data Sheet"
JC
Junction code
STD
CONT: Switching for continuation
HOLD: Hold-on switching (the controller holds the end-of-segment setpoint
when the segment is completed, to perform control).
LOCAL: Local-mode switching (the controller switches to a local setpoint when
the segment is completed).
REM: Remote-mode switching (the controller switches to a remote setpoint
when the segment is completed).
W.SW1 to W.SW5: Wait during switching between segments.
W.IV1 to W.IV5: Wait within a segment interval.
W.SL1 to W.SL5: Segment switching (the controller switches to a local setpoint
when the segment is completed after release.) (5 groups)
W.SR1 to W.SR5: Segment switching (the controller switches to a remote
setpoint when the segment is completed after release.) (5 groups)
PLK.1 to PLK.30: Linked to patterns 1 to 30.
INS.: Allows a segment to be added to the end of a specified segment.
DEL.: Allows a specified segment to be deleted.
CONT
See
Sheet"Program
Data Sheet"
PV.TY1
~
PV.TY8
PV event-1 to -8 type
STD
OFF: Disable
(Energized)
1: PV high limit,
2: PV low limit,
3: SP high limit,
4: SP low limit,
5: Deviation high limit,
6: Deviation low limit,
7: Deviation high and low limits,
8: Deviation within high and low limits,
9: Target SP high limit,
10: Target SP low limit,
11: Target SP deviation high limit,
12: Target SP deviation low limit,
13: Target SP deviation high and low limits,
14: Target SP deviation within high and low limits,
15: OUT high limit,
16: OUT low limit,
17: Cooling-side OUT high limit,
18: Cooling-side OUT low limit
* Add 100 for "de-energized". For example, when the PV high limit is de-
energized, the setting is 101.
OFF
See
Sheet"Program
Data Sheet"
PV.EV1
~
PV.EV8
PV event-1 to -8 setpoint
STD
Set a display value of setpoint of PV alarm, SP alarm, deviation alarm, or
output alarm.
-19999 to 30000 (Set a value within the input range.)
Decimal point position depends on the input type.
0
See
Sheet"Program
Data Sheet"
TME1
~
TME16 Start condition of time event 1 to 16
STD
ON: Start ON state
OFF: Start OFF state
OFF
See
Sheet"Program
Data Sheet"
T.ON1
~
T.ON16 On time of time event 1 to 16
STD
-
See
Sheet"Program
Data Sheet"
T.OF1
~
T.OF16 Off time of time event 1 to 16
STD
-
See
Sheet"Program
Data Sheet"
Local Setting
Program pattern-2
retransmission
(PT2.G=ON)
Menu
Symbol
Name
Display level
Setting range
Initial value
User setting
User setting
LOC
LSP
Local target setpoint
EASY
0.0 to 100.0% of PV input range (EU)
(Setting range: P.RL to P.RH)
P.RL
L.PID
PID number selection for local mode operation
EASY
Set a PID group number to use.
1 to 8
* Available only for the L.PID when ZON = 0 or 5.
* If set to “Local PID selection,” local PID is selected irrespective of the
operation modes.
1
L.TY1
Local event-1 type
STD
OFF: Disable
(Energized)
1: PV high limit,
2: PV low limit,
3: SP high limit,
4: SP low limit,
5: Deviation high limit,
6: Deviation low limit,
7: Deviation high and low limits,
8: Deviation within high and low limits,
9: Target SP high limit,
10: Target SP low limit,
11: Target SP deviation high limit,
12: Target SP deviation low limit,
13: Target SP deviation high and low limits,
14: Target SP deviation within high and low limits,
15: OUT high limit,
16: OUT low limit,
17: Cooling-side OUT high limit,
18: Cooling-side OUT low limit
* Add 100 for "de-energized". For example, when the PV high limit is de-
energized, the setting is 101.
OFF
L.EV1
Local event-1 setpoint
STD
Set a display value of setpoint of PV alarm, SP alarm, deviation alarm, or
output alarm.
-19999 to 30000 (Set a value within the input range.)
Decimal point position depends on the input type
0
L.TY2
Local event-2 type
STD
Same as L.TY1
OFF
L.EV2
Local event-2 setpoint
STD
Same as L.EV1
0
L.TY3
Local event-3 type
STD
Same as L.TY1
OFF
L.EV3
Local event-3 setpoint
STD
Same as L.EV1
0
L.TY4
Local event-4 type
STD
Same as L.TY1
OFF
L.EV4
Local event-4 setpoint
STD
Same as L.EV1
0
L.TY5
Local event-5 type
STD
Same as L.TY1
OFF
L.EV5
Local event-5 setpoint
STD
Same as L.EV1
0
L.TY6
Local event-6 type
STD
Same as L.TY1
OFF
L.EV6
Local event-6 setpoint
STD
Same as L.EV1
0
L.TY7
Local event-7 type
STD
Same as L.TY1
OFF
L.EV7
Local event-7 setpoint
STD
Same as L.EV1
0
L.TY8
Local event-8 type
STD
Same as L.TY1
OFF
L.EV8
Local event-8 setpoint
STD
Same as L.EV1
0
Program Editing
Menu
Symbol
Name
Display level
Setting range
Initial value
User setting
EDIT
ALL.S
Number of remaining unused segments
PRO
0 to 300 (Display only)
300
PTN.S
Pattern number designation for comfirming
number of segments
PRO
Specify the numbers of program pattern to display in parameter USE.S.
1 to 30
0
USE.S
Number of segments within a pattern
PRO
Can be displayed when the parameter number specify in parameter PTN.S.
(Display only)
0: disable
1 to 99
-
CPY.S
Source-of-copying pattern number designation
PRO
Specify the number of the sourceof-copying program pattern. (1 to 30)
0
CPY.D
Target-of-copying pattern number designation
PRO
Specify the target-of-copying program pattern. (1 to 30)
0
CLR.P
Program pattern clearance
PRO
Specify the number of the program pattern to be cleared. (1 to 30)
0
Alarm Setpoint Setting
Menu
Symbol
Name
Display level
Setting range
Initial value
User setting
AL
A1
Alarm-1 setpoint
EASY
0
A2
Alarm-2 setpoint
EASY
0
A3
Alarm-3 setpoint
EASY
0
A4
Alarm-4 setpoint
EASY
0
A5
Alarm-5 setpoint
EASY
0
A6
Alarm-6 setpoint
EASY
0
A7
Alarm-7 setpoint
EASY
0
A8
Alarm-8 setpoint
EASY
0
These alarms work irrespective of the operation mode.
Set a display value of setpoint of PV alarm, SP alarm, deviation alarm, output
alarm, or velocity alarm.
-19999 to 30000 (Set a value within the input range.)
Decimal point position depends on the input type.
-: Unregistered
0.01 to 999.59 (“hour.minute” or “minute.second”)
* Available only within the segment time.
* OFF when the operation mode is changed to the mode except the program
operation.
* Use the parameter TMU to set the time unit. (Common in the instrument.)