Program Pattern Setup Charts

CAUTION

You can register max. 99 program segments with the UP55A controller. Create as many copies of the chart as necessary.

System name

Maximum value of PV input range / Maximum value of PV input scale 

       

Program No.

Unit (

      

)

Program name
Model
Serial No.

A program pattern can be drawn in the right table.

Minimum value of PV input range / Minimum value of PV input scale 

       

Parameter symbol

User settings

Parameter symbol

Parameter name

TMU

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

SEG.T

TSP

Final target setpoint

ZON

TSP

Final target setpoint for Program pattern-2 retransmission

PT2.G

TIME

Segment time setting

TM.RT

Segment ramp-rate setting

S.PID

Segment PID number selection

JC

Junction code

PV.TY1

PV event-1 type

PV.EV1

PV event-1 setpoint

Parameter symbol

User settings

PV.TY2

PV event-2 type

SSP

PV.EV2

PV event-2 setpoint

SSP

PV.TY3

PV event-3 type

STC

PV.EV3

PV event-3 setpoint

WT.SW1

PV.TY4

PV event-4 type

WZ.UP1

PV.EV4

PV event-4 setpoint

WZ.LO1

PV.TY5

PV event-5 type

WT.TM1

PV.EV5

PV event-5 setpoint

WT.SW2

PV.TY6

PV event-6 type

WZ.UP2

PV.EV6

PV event-6 setpoint

WZ.LO2

PV.TY7

PV event-7 type

WT.TM2

PV.EV7

PV event-7 setpoint

WT.SW3

PV.TY8

PV event-8 type

WZ.UP3

PV.EV8

PV event-8 setpoint

WZ.LO3

TME1

Start condition of time event 1

WT.TM3

T.ON1

On time of time event 1

WT.SW4

T.OF1

Off time of time event 1

WZ.UP4

TME2

Start condition of time event 2

WZ.LO4

T.ON2

On time of time event 2

WT.TM4

T.OF2

Off time of time event 2

WT.SW5

TME3

Start condition of time event 3

WZ.UP5

T.ON3

On time of time event 3

WZ.LO5

T.OF3

Off time of time event 3

WT.TM5

TME4

Start condition of time event 4

R.CYCL

T.ON4

On time of time event 4

R.STRT

T.OF4

Off time of time event 4

R.END

TME5

Start condition of time event 5

T.ON5

On time of time event 5

T.OF5

Off time of time event 5

TME6

Start condition of time event 6

T.ON6

On time of time event 6

T.OF6

Off time of time event 6

TME7

Start condition of time event 7

T.ON7

On time of time event 7

T.OF7

Off time of time event 7

TME8

Start condition of time event 8

T.ON8

On time of time event 8

T.OF8

Off time of time event 8

TME9

Start condition of time event 9

T.ON9

On time of time event 9

T.OF9

Off time of time event 9

TME10

Start condition of time event 10

T.ON10

On time of time event 10

T.OF10

Off time of time event 10

TME11

Start condition of time event 11

T.ON11

On time of time event 11

T.OF11

Off time of time event 11

TME12

Start condition of time event 12

T.ON12

On time of time event 12

T.OF12

Off time of time event 12

TME13

Start condition of time event 13

T.ON13

On time of time event 13

T.OF13

Off time of time event 13

TME14

Start condition of time event 14

T.ON14

On time of time event 14

T.OF14

Off time of time event 14

TME15

Start condition of time event 15

T.ON15

On time of time event 15

T.OF15

Off time of time event 15

TME16

Start condition of time event 16

T.ON16

On time of time event 16

T.OF16

Off time of time event 16

Parameter name

Program time unit
Segment setting method

The following parameters are necessary to be set before programming.
Note that the program is deleted if TMU or SEG.T is changed after creating
programs.

Zone PID selection
Program pattern-2 retransmission

Parameter name

Starting target setpoint

The following parameters are common parameters for the program
pattern specified.

Starting target setpoint (for program pattern-2 retransmission)
Start code
Wait function ON/OFF 1
Upper-side wait zone 1
Lower-side wait zone 1
Wait time 1
Wait function ON/OFF 2
Upper-side wait zone 2
Lower-side wait zone 2
Wait time 2
Wait function ON/OFF 3
Upper-side wait zone 3

Upper-side wait zone 5

Lower-side wait zone 3
Wait time 3
Wait function ON/OFF 4
Upper-side wait zone 4

Note that the program patterns are all deleted if the settings change after creating program patterns.
Be sure to check the PV input range, Program time unit (TMU), and Segment setting method (SEG.T) before creating.

Segments

Repeat cycle end segment number

Lower-side wait zone 5
Wait time 5
Number of repeat cycles
Repeat cycle start segment number

Lower-side wait zone 4
Wait time 4
Wait function ON/OFF 5

Page 24 / 25

Summary of Contents for UTAdvanced UP55A

Page 1: ...UTAdvanced UP55A Program Controller Parameter Maps and Lists TI 05P02C41 01EN Copyright July 2011 1st Edition July 2011 Page 1 25...

Page 2: ...eet describes the setting range and initial value of operation parameters and setup parameters There is a column for user settings Program Data Sheet This sheet can be used for recording the setting v...

Page 3: ...inal area E1 to E4 in the Parameter Setting Display Displays a parameter symbol Displays the setting conditions of the parameter display level function Parameter display level EASY PRO Easy setting mo...

Page 4: ...t is blinking to move between digits according to the parameter Description Used to switch the Operation Displays Press the key in the Operation Display to switch the provided Operation Displays Press...

Page 5: ...parameter and operation status Parameter Display Transition and Setup Operation To move to the Operation Parameter Setting Display To move to the Setup Parameter Setting Display To move to the Operati...

Page 6: ...he Up or Down arrow key to change the setpoint 6 Press the SET ENTER key to register the setpoint the setpoint stops blinking This completes the setting procedure How to Cancel Parameter Setting To ca...

Page 7: ...How to Set Parameter Setpoint Numeric Value Setting Selection Data Setting Time minute second Setting Page 7 25...

Page 8: ...14 segments Alphabet Symbol display and Data display 11 segments Alphabet Group display 7 segments Alphabet PV display 14 segments Symbol The following shows the parameter symbols menu symbols alphanu...

Page 9: ...CYCL 1 T ON16 99 T ON16 VT7 R STRT 1 T OF16 99 T OF16 VT8 R END END END HY1 END HY2 HY3 HY4 HY5 HY6 HY7 Symbol Corresponding parameters are displayedin all modes HY8 1 PYS1 2 PYS2 3 PYS3 4 PYS4 END MO...

Page 10: ...unction Numbering DI1 DI3 Contact Type Setting DI Setting E1 terminal area DI Setting E2 terminal area DI Setting E3 terminal area DI Setting E4 terminal area AL1 AL3 Function Registration DO Setting...

Page 11: ...Data Sheet WT SW1 Wait function ON OFF 1 STD OFF Disable ON Enable OFF See Sheet Program Data Sheet WZ UP1 Upper side wait zone 1 STD 0 5 of PV input range See Sheet Program Data Sheet WZ LO1 Lower s...

Page 12: ...ern 2 retransmission PT2 G ON Menu Symbol Name Display level Setting range Initial value User setting User setting LOC LSP Local target setpoint EASY 0 0 to 100 0 of PV input range EU Setting range P...

Page 13: ...hysteresis EASY 10 HY4 Alarm 4 hysteresis EASY 10 HY5 Alarm 5 hysteresis EASY 10 HY6 Alarm 6 hysteresis EASY 10 HY7 Alarm 7 hysteresis EASY 10 HY8 Alarm 8 hysteresis EASY 10 DYN1 Alarm 1 On delay time...

Page 14: ...haracteristic changes compared with response mode 3 Hunting suppressing function response mode Enables quick follow up and short converging time of PV for the changed SP 4 Overshoot suppressing functi...

Page 15: ...segment linearizer 3 output 2 PRO 0 0 A3 10 segment linearizer 3 input 3 PRO 0 0 B3 10 segment linearizer 3 output 3 PRO 0 0 A4 10 segment linearizer 3 input 4 PRO 0 0 B4 10 segment linearizer 3 outp...

Page 16: ...of PV input scale EASY Depends on the input type SL Minimum value of PV input scale EASY Depends on the input type BSL PV input burnout action STD OFF Disable UP Upscale DOWN Downscale Depends on the...

Page 17: ...SH Maximum value of AIN4 aux analog input scale EASY Depends on the input type SL Minimum value of AIN4 aux analog input scale EASY Depends on the input type BSL AIN4 aux analog input burnout action S...

Page 18: ...UT current output range STD 4 20 OU2 A OUT2 current output range STD 4 20 RET A RET current output range STD 4 20 Heater Break Alarm Setting Menu Symbol Name Display level Setting range Initial value...

Page 19: ...10M 10 minutes 30M 30 minutes 60M 60 minutes OFF When each parameter is displayed the terminal area E3 is displayed on Group display DeviceNet Communication Setting Menu Symbol Name Display level Set...

Page 20: ...when there has been no keystroke operation for 5 minutes OFF ON ON MLSD Least significant digital mask of PV display STD OFF With least significant digit ON Without least significant digit OFF Set a d...

Page 21: ...FF INIT INIT menu lock PRO OFF VER VER menu lock PRO OFF LVL LVL menu lock PRO OFF MODE MODE menu lock PRO OFF CS CS menu lock PRO OFF PROG PROG menu lock PRO OFF LOC LOC menu lock PRO OFF EDIT EDIT m...

Page 22: ...et output STD 0 Preset output 1 0 output 2 100 output Set preset output value when the input burnout or ADC error occurs Manual output is prioritized when the input burnout occurs in MAN 0 C GRN Respo...

Page 23: ...3 ECU 3 version EASY ECU4 ECU 4 version EASY PARA Parameter version EASY H VER Product version EASY SER1 Serial number 1 EASY SER2 Serial number 2 EASY MAC1 MAC address 1 EASY MAC2 MAC address 2 EASY...

Page 24: ...T ON7 On time of time event 7 T OF7 Off time of time event 7 TME8 Start condition of time event 8 T ON8 On time of time event 8 T OF8 Off time of time event 8 TME9 Start condition of time event 9 T O...

Page 25: ...on of time event 10 T ON10 On time of time event 10 T OF10 Off time of time event 10 TME11 Start condition of time event 11 T ON11 On time of time event 11 T OF11 Off time of time event 11 TME12 Start...