AIN2 Aux. Analog Input Setting
Menu
Symbol
Name
Display level
Setting range
Initial value
User setting
AIN2
IN
AIN2 aux. analog input type
EASY
0.4-2V: 0.400 to 2.000 V
1-5V: 1.000 to 5.000 V
0-2V: 0.000 to 2.000 V
0-10V: 0.00 to 10.00 V
0-125: 0.000 to 1.250 V
1-5V
UNIT
AIN2 aux. analog input unit
EASY
-: No unit
C: Degree Celsius
-: No unit
--: No unit
---: No unit
F: Degree Fahrenheit
C
RH
Maximum value of AIN2 aux. analog input
range
EASY
Depends on the input type
RL
Minimum value of AIN2 aux. analog input range EASY
Depends on the input type
SDP
AIN2 aux. analog input scale decimal point
position
EASY
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
Depends on the input type
SH
Maximum value of AIN2 aux. analog input scale EASY
Depends on the input type
SL
Minimum value of AIN2 aux. analog input scale EASY
Depends on the input type
BSL
AIN2 aux. analog input burnout action
STD
OFF: Disable
UP: Upscale
DOWN: Downscale
Depends on the input type
A.BS
AIN2 aux. analog input bias
PRO
-100.0 to 100.0% of AIN2 input range span (EUS)
0.0 % of AIN2 input range
span
A.FL
AIN2 aux. analog input filter
PRO
OFF, 1 to 120 s
OFF
A.SR
AIN2 aux. analog input square root extraction
PRO
OFF: No square root extraction.
1: Compute the square root. (The slope equals “1.”)
2: Compute the square root. (The slope equals “0.”)
OFF
A.LC
AIN2 aux. analog input low signal cutoff
PRO
0.0 to 5.0%
1.0%
DI6.D
DI26 contact type
PRO
0: The assigned function is enabled when the contact is closed.
1: The assigned function is enabled when the contact is opened.
0
When each parameter is displayed, the terminal area (E2) is displayed on Group display.
AIN4 Aux. Analog Input Setting
Menu
Symbol
Name
Display level
Setting range
Initial value
User setting
AIN4
IN
AIN4 aux. analog input type
EASY
0.4-2V: 0.400 to 2.000 V
1-5V: 1.000 to 5.000 V
0-2V: 0.000 to 2.000 V
0-10V: 0.00 to 10.00 V
0-125: 0.000 to 1.250 V
1-5V
UNIT
AIN4 aux. analog input unit
EASY
-: No unit
C: Degree Celsius
-: No unit
--: No unit
---: No unit
F: Degree Fahrenheit
C
RH
Maximum value of AIN4 aux. analog input
range
EASY
Depends on the input type
RL
Minimum value of AIN4 aux. analog input range EASY
Depends on the input type
SDP
AIN4 aux. analog input scale decimal point
position
EASY
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
Depends on the input type
SH
Maximum value of AIN4 aux. analog input scale EASY
Depends on the input type
SL
Minimum value of AIN4 aux. analog input scale EASY
Depends on the input type
BSL
AIN4 aux. analog input burnout action
STD
OFF: Disable
UP: Upscale
DOWN: Downscale
Depends on the input type
A.BS
AIN4 aux. analog input bias
PRO
-100.0 to 100.0% of AIN4 input range span (EUS)
0.0 % of AIN4 input range
span
A.FL
AIN4 aux. analog input filter
PRO
OFF, 1 to 120 s
OFF
A.SR
AIN4 aux. analog input square root extraction
PRO
OFF: No square root extraction.
1: Compute the square root. (The slope equals “1.”)
2: Compute the square root. (The slope equals “0.”)
OFF
A.LC
AIN4 aux. analog input low signal cutoff
PRO
0.0 to 5.0%
1.0%
DI6.D
DI46 contact type
PRO
0: The assigned function is enabled when the contact is closed.
1: The assigned function is enabled when the contact is opened.
0
When each parameter is displayed, the terminal area (E4) is displayed on Group display.
Input Range/SP Limiter Setting
Menu
Symbol
Name
Display level
Setting range
Initial value
User setting
MPV
P.UNI
Control PV input unit
STD
-: No unit
C: Degree Celsius
-: No unit
--: No unit
---: No unit
F: Degree Fahrenheit
Same as PV input unit
P.DP
Control PV input decimal point position
STD
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
Depends on the input type
P.RH
Maximum value of control PV input range
STD
Depends on the input type
P.RL
Minimum value of control PV input range
STD
Depends on the input type
SPH
SP high limit
STD
100.0 % of PV input range
SPL
SP low limit
STD
0.0 % of PV input range
Depends on the input type.
Set the range of a voltage signal that is applied.
The scale across which the voltage signal is actually controlled should be set
using the maximum value of input scale (SH) and minimum value of input
scale (SL).
(Input is always 0% when RL = RH.)
-19999 to 30000, (SL<SH), | SH - SL |
≤
30000
Depends on the input type.
Set the range of a voltage signal that is applied.
The scale across which the voltage signal is actually controlled should be set
using the maximum value of input scale (SH) and minimum value of input
scale (SL).
(Input is always 0% when RL = RH.)
-19999 to 30000, (SL<SH), | SH - SL |
≤
30000
-19999 to 30000, (P.RL<P.RH), | P.RH - P.RL |
≤
30000
0.0 to 100.0% of PV input range (EU), (SPL<SPH)
Place limits on the program setpoints or the local setpoints when the controller
is in program operation.
* Places the limit on the program setpoint, local setpoint, or remote setpoint
during program operation.
* When LP2 lamp is on, SPH and SPL limit the program setpoint for program
pattern 2 retransmission.