18-15
IM 05P04D41-01EN
Parameters
18
Display Function Setting Menu (Menu: DISP) (Continued from previous page)
Parameter
symbol
Name
Display
level
Setting range
Initial value
GUID
Guide display
ON/OFF
STD
OFF: Nondisplay
ON: Display
ON
HOME
Home Operation
Display setting
PRO
PV: PV Display
SP: SP Display
SP
ECO
Economy mode
STD
OFF: Disable
1: Economy mode ON (All indications
except PV display OFF)
2: Economy mode ON (All indications
OFF)
3: Brightness 10 % (All indications)
OFF
BRI
Brightness
EASY
(Dark) 1 to 5 (Bright)
3
B.PVW
White brightness
adjustment of PV
display
PRO
Adjusts the white brightness of PV
display.
(Dark) -4 to 4 (Bright)
0
B.PVR
Red brightness
adjustment of PV
display
PRO
Adjusts the red brightness of PV display.
(Dark) -4 to 4 (Bright)
0
B.SP
Brightness
adjustment of
Setpoint display
PRO
Adjusts the brightness of SP display.
(Dark) -4 to 4 (Bright)
0
B.BAR
Brightness
adjustment of
Bar-graph
display
PRO
Adjusts the brightness of EXCEED lamp
and OUT lamp.
(Dark) -4 to 4 (Bright)
0
B.STS
Brightness
adjustment of
Status indicator
PRO
Adjusts the brightness of Status
indicator.
(Dark) -4 to 4 (Bright)
0
D.CYC
Display update
cycle
PRO
1: 100 ms
2: 200 ms
3: 500 ms
4: 1 s
5: 2 s
2
OP.JP
Autoreturn to
operation display
PRO
Automatically returned to the Operation
Display when there has been no
keystroke operation for 5 minutes.
OFF, ON
ON
MLSD
Least significant
digital mask of
PV display
STD
OFF: With least significant digit
ON: Without least significant digit
OFF
Key Lock Setting Menu (Menu: KLOC)
Parameter
symbol
Name
Display
level
Setting range
Initial value
COM.W
Communication
write enable/
disable
STD
OFF: Enable, ON: Disable
OFF
DATA
Front panel
parameter data
key lock
STD
OFF: Unlock
ON: Lock
OFF