18-11
IM 05P04D41-01EN
Parameters
18
Output Setting Menu (Menu: OUT)
Parameter
symbol
Name
Display
level
Setting range
Initial value
RTS
Retransmission
output type of RET
EASY
OFF: Disable
PV1: PV
SP1: SP
PV1
RTH
Maximum value
of retransmission
output scale of RET
STD
When RTS = PV1, SP1
RTL + 1 digit to 30000
-19999 to RTH - 1 digit
Decimal point position:
When RTS=PV1 or SP1 decimal
point position is same as that of
PV input.
When RTS=PV, decimal point
position is same as that of PV
input scale.
100 % of PV
input range
RTL
Minimum value
of retransmission
output scale of RET
STD
0 % of PV
input range
RET.A
RET current output
range
STD
4-20: 4 to 20 mA
0-20: 0 to 20 mA
20-4: 20 to 4 mA
20-0: 20 to 0 mA
4-20