<5. Parameters>
5-7
IM 05F01D02-41E
1st Edition : May 31,2000-00
■
Useful Operating Display (SELECT Display)
Registering frequently changed parameters in the SELECT display after ordinary operating
displays will allow you to change settings easily. A maximum four displays can be regis-
tered.
S E T / E N T
key
S E T / E N T
key
PV display
Ordinary operating
displays (example)
Alarm-1 setting
display (example)
Useful
operating display
(SELECT display)
P V
AL1
2
3
4
S E T / E N T
P V
AL1
2
3
4
S E T / E N T
<Setting Method>
Set the parameter numbers (D register numbers) you wish to register for setup parameters
C.S1 to C.S4.
●
Numbers for Registration with SELECT Display
Operating Parameter
Registration Number
Alarm-1 setpoint (A1)
Alarm-2 setpoint (A2)
Alarm-3 setpoint (A3)
Alarm-4 setpoint (A4)
231
232
233
234
Bias (BS)
243
Filter (FL)
244
Setup Parameter
Registration Number
Alarm-1 hysteresis
Alarm-2 hysteresis
Alarm-3 hysteresis
Alarm-4 hysteresis
919
920
921
922