APPENDIX 2. APPLICATION, SETTING AND CHANGE OF BASIC PARAMETERS
A-13
All Rights Reserved. Copyright © 2006, Rota Yokogawa
IM 01R01B02-01E-E 5th edition October 01, 2020 -00
A2.3 Setting the AI Function Blocks
The AI function block outputs the flow rate signals.
(1) Setting the output scale
Access the OUT_SCALE parameter.
Set the necessary unit of output to Units Index on OUT_SCALE. Set an output value corresponding to the
higher range value to EU at 100 % on OUT_SCALE.
Set an output value corresponding to the lower range value to EU at 0 % on OUT_SCALE.
Optional: Set the decimal position to Decimal Point.
Example:
To set the output to 0.00 to 120.00 kg/h,
1. Set kg/h (1324)* to sub-parameter Units_Index on parameter OUT_SCALE.
2. Set 120 to sub-parameter EU_at_100 % on parameter OUT_SCALE.
3. Set 0 to EU at 0% on OUT_SCALE.
4. Set 2 to sub-parameter Decimal_Point on parameter OUT_SCALE.
* Each unit is expressed using a 4-digit numeric code.
Refer to chapter 5.4 for comparison.
(
2) Simulation
The AI Function Block could be simulated by using the simulation functionality.
If simulation is enabled, AI block uses SIMULATE_STATUS and SIMULATE_VALUE as the input, and if
disabled, the AI block uses the Status and Value of the TB's Process Variable selected by the channel as
input.
Access the SIMULATE sub-parameter Simulate_Enabled.
Set to enabled (“1”).
Access the SIMULATE sub-parameter Simulate_Status.
Set the status code.
Access the SIMULATE sub-parameter Simulate_Value.
Set an optional input value.
Access the SIMULATE sub-parameter Simulate_Enabled.
Set to disabled (“0”).