
APPENDIX 2. APPLICATION, SETTING AND CHANGE OF BASIC PARAMETERS
A-11
All Rights Reserved. Copyright © 2006, Rota Yokogawa
IM 01R01B02-01E-E 5th edition October 01, 2020 -00
Appendix 2. Application, Setting and
Change of basic Parameters
A2.1 Applications and Selection of Basic Parameters
Setting Item
(applicable parameters )
Summary
Tag No.
Sets TAG_DESC for each block tag.
Up to 32 alphanumeric characters can be set. See appendix 1.
Calibration range setup
(PV_SCALE)
Sets the range of input from the transducer block corresponding to the 0 % and 100 % points in opera-
tion within the AI Function Block. The calibrated range (0 % and 100 %) is the factory default setting.
Output scale setup
(OUT_SCALE)
Sets the scale of output corresponding to the 0 % and 100 % points in operation within the AI function
Block. It is possible to set a unit and scale range that differs from the measurement range.
Sets the range unit, input value of the 0 % point (lower limit of output scale), input value of the 100 %
point (upper limit of output scale).
Simulation setup
(SIMULATE)
Performs simulation of the AI Function Block.
The input value and status for the Variable Process (channel) can be set.
It is recommended to use this parameter for loop checks and other purposes.
Output signal low cut setup
Sets the low cut between 5 % to 15 % of VOLUME_FLOW_HI_LIMIT or MASS_FLOW_HI_LIMIT.