<APPENDIX 1. LIST OF PARAMETERS FOR EACH BLOCK OF RAMC>
A-8
All Rights Reserved. Copyright © 2006, Rota Yokogawa
IM 01R01B02-01E-E 5th edition October 01, 2020-00
Abs.
Index
Parameter
Sub-
Parameter
Label
Data Type/
Structure
Read/
Write
Initial value
Functional Description
33
VOLUME_FLOW
-
101
R/-
-
Indicates the measured volume flow
Value
Volume Flow
Float
R/-
-
Volume flow value
Status
Volume Flow
Status
Unsigned8
R/-
-
Volume flow status
34
VOLUME_FLOW_
UNITS
Volume Flow Unit
Unsigned16
R/W
Det. by ordered
scale
Volume flow unit selection and enabling
of measured variable (disables mass
flow)
35
VOLUME_FLOW_
LO_LIMIT
Volume Flow Low
Limit
Float
R/W
0 % of flow span
Sensor's lower range value (volume flow)
36
VOLUME_FLOW_
HI_LIMIT
Volume Flow High
Limit
Float
R/W
100 % of flow span Sensor's upper range value (volume flow)
37
MASS_FLOW
-
101
R/-
-
Indicates the measured mass flow
Value
Mass Flow
Float
R/-
-
Mass flow value
Status
Mass Flow Status
Unsigned8
R/-
-
Mass flow status
38
MASS_FLOW_
UNITS
Mass Flow Unit
Unsigned16
R/W
Det. by ordered
scale
Mass flow unit selection and enabling
of measured variable (disables volume
flow)
39
MASS_FLOW_
LO_LIMIT
Mass Flow Low
Limit
Float
R/W
0 % of flow span
Sensor's lower range value (mass flow)
40
MASS_FLOW_HI_
LIMIT
Mass Flow High
Limit
Float
R/W
100 % of flow span Sensor's upper range value (mass flow)
45
TEMPERATURE
-
101
R/-
-
Measured on board temperature
Value
Temperature
Float
R/-
According to
ambient
temperature
Indicates the on board temperature
value
Status
-
Unsigned8
R/-
0x80: Good
Not supported
46
TEMPERATURE_
UNITS
Temperature Unit
Unsigned16
R/W
1001: °C
On board temperature unit selection
69
OPER_VISCOSITY
Viscosity
Float
R/-
Det. by ordered
scale
Indicates fluid's viscosity configuration
value
70
OPER_VISCOSITY
_UNIT
-
Unsigned16
R/-
Det. by ordered
scale
Configurated unit of fluid's viscosity
71
OPER_PRESSURE
Pressure
Float
R/-
Det. by ordered
scale
Indicates fluid's pressure configuration
value
72
OPER_PRESSURE
_UNIT
-
Unsigned16
R/-
Det. by ordered
scale
Configurated unit of fluid's pressure
73
OPER_PRESSURE
_REF
Ref. Pressure
Float
R/-
Det. by ordered
scale
Indicates fluid's pressure reference
configuration value
74
OPER_PRESSURE
_REF_UNIT
-
Unsigned16
R/-
Det. by ordered
scale
Configurated unit of fluid's pressure
reference
75
OPER_
TEMPERATURE
Temperature
Float
R/-
Det. by ordered
scale
Indicates fluid's process temperature
configuration value
76
OPER_
TEMPERATURE_
UNIT
-
Unsigned16
R/-
Det. by ordered
scale
Configurated unit of fluid's process
temperature configuration unit
77
OPER_
CONDITION
Oper. Condition
Unsigned8
R/-
Det. by ordered
scale
Indicates configured fluid's pressure
operation condition
78
OPER_FLUID_
PHASE
Fluid Phase
Unsigned8
R/-
Det. by ordered
scale
Indicates fluid's operation condition
79
OPER_FLOW_
REFERENCE
Flow Reference
Unsigned8
R/-
Det. by ordered
scale
Indicates fluid's operation flow reference
80
DEVICE_SERIAL_
NO
Serial Number
(S/N)
OctetString
R/-
Det. by ordered
device
Indicates the serial number of the
device
81
DEVICE_MODEL_
CODE
Model Code
OctetString
R/-
Det. by ordered
device
Indicates the model code of the device
82
OPER_FLUID_
NAME
Fluid Name
OctetString
R/-
Det. by ordered
scale
Indicates fluid's name
83
TOTALIZER
Totalizer
Float
R/-
0
Indicates totalized value (volume or
mass) of the enabled process variable
84
TOTALIZER_UNIT
Totalizer Unit
Unsigned16
R/W
Det. by ordered
scale
Indicates totalizer unit
85
TOTALIZER_
RESET
Totalizer Reset
Unsigned8
R/W
-
Performs totalizer reset to zero
86
RESET_ERROR_
BIT
Reset Errors
Unsigned8
R/W
-
Execution resets specific error bits
87
DIST_OPTION_
A16
Device Version
Unsigned8
R/-
Det. by ordered
device
Indicates the mechanical indicator
version (Distance: option /A16)
88
SCALE_SPAN_
VALUE
Scale 100% Value
Float
R/-
Det. by ordered
scale
Indicates flow value printed on scale
(at 100 %)
89
SOFT_REVISION
FW Version
OctetString
R/-
e.g. V1.00
Indicates transmitter's firmware version