<APPENDIX 1. LIST OF PARAMETERS FOR EACH BLOCK OF RAMC>
A-5
All Rights Reserved. Copyright © 2006, Rota Yokogawa
IM 01R01B02-01E-E 5th edition October 01, 2020 -00
Abs.
Index
Parameter
Sub-
Parameter
Label
Data Type/
Structure
Read/
Write
Initial value
Functional Description
Value
OUT Value
Float
R/W
0
Indication and input of value (setting
dependent)
Status
OUT Status
Unsigned8
R/W
0x80: GOOD
Indication and input of status (setting
dependent)
27
PV_SCALE
-
Array of
Float
R/W
-
Conversion of the process variable into
percent using the high and low scale
values
Array1
PV Scale Upper
Value
Float
R/W
Det. by ordered
scale
Input and indication of the value corre-
sponding to 100 % of scale
Array2
PV Scale Lower
Value
Float
R/W
0
Input and indication of the value corre-
sponding to 0 % of scale
28
OUT_SCALE
-
DS-36
R/W
-
Input and indication of process
variable's scale
EU_at_100%
OUT Scale Upper
Value
Float
R/W
Det. by ordered
scale
Corresponding OUT scale value to
100 %
EU_at_0%
OUT Scale Lower
Value
Float
R/W
0
Corresponding OUT scale value to 0 %
Units_Index
Unit
Unsigned16
R/W
Det. by ordered
scale
Indication and setting of the OUT scale
unit
Decimal_Point
Decimal Point
Integer8
R/W
2
Memo of the number of valid digits
below decimal point
29
LIN_TYPE
Characterization
Type
Unsigned8
R/W
0: No Linearisation
Input and indication of linearization type
30
CHANNEL
Channel
Unsigned16
R/W
Det. by ordered
scale
Reference to the active Transducer
Block which provides the measurement
value
32
PV_FTIME
Filter Time Constant Float
R/W
0.0
Time constant of a single exponential
filter for the PV, in seconds
33
FSAFE_TYPE
Fail Safe Mode
Unsigned8
R/W
1
In case of BAD status the OUT is adju-
sted based on the following settings:
0: Value: FSAFE_VALUE, Status:
UNCERTAIN - Substitute Value
1: Value: last stored valid value, Status:
UNCERTAIN-last usable value
2: Value: actual, Status: no adjustment
34
FSAFE_VALUE
Fail Safe Default
Value
Float
R/W
0
Default value for the OUT parameter in
case of BAD status.
35
ALARM_HYS
Limit Hysteresis
Float
R/W
0.5
Absolute value of OUT value must re-
turn within the alarm limits before alarm
condition clears (in OUT scale unit).
37
HI_HI_LIM
Upper Limit Alarm
Float
R/W
3.4038:
INF
Setting of the upper limit alarm value (in
OUT scale unit)
39
HI_LIM
Upper Limit
Warning
Float
R/W
3.4038:
INF
Setting of the upper limit warning value
(in OUT scale unit)
41
LO_LIM
Lower Limit
Warning
Float
R/W
-3.4038:
-INF
Setting of the lower limit warning value
(in OUT scale unit)
43
LO_LO_LIM
Lower Limit Alarm
Float
R/W
-3.4038:
-INF
Setting of the lower limit alarm value (in
OUT scale unit)
46
HI_HI_ALM
-
DS-39
R/-
-
State of the upper alarm limit
Unacknowledged
Upper Unack.
Alarms
Unsigned8
R/-
0
For future use (not available)
Alarm_State
Upper Alarm
Status
Unsigned8
R/-
0: No Alarm
Indicates the alarm status
Time Stamp
-
Time Value
R/-
0
For future use (not available)
Subcode
-
Unsigned16
R/-
0
For future use (not available)
Value
Upper Alarm
Output Value
Float
R/-
0
Indicates the value which caused the
alarm
47
HI_ALM
-
DS-39
R/-
-
State of the upper warning limit
Unacknowledged
Upper Unack.
Warnings
Unsigned8
R/-
0
For future use (not available)
Alarm_State
Upper Warning
Status
Unsigned8
R/-
0: No Warning
Indicates the warning status
Time Stamp
-
Time Value
R/-
0
For future use (not available)
Subcode
-
Unsigned16
R/-
0
For future use (not available)
Value
Upper Warning
Output Value
Float
R/-
0
Indicates the value which caused the
warning
* Writable in block mode "MAN" only!