9-3
IM 34M6H55-02E
1st Edition : Apr 1, 2002-00
9.3 Encoder Z-phase Input
This is the encoder Z-phase input. It is used only during an origin search. You may also
connect a RS422A compliant differential signal.
Table 9.4 Signal Specifications
Item Specifications
Insulation method
Photocoupler-isolated
Input impedance
240
Ω
Rated input voltage
(operating voltage range)
5 V DC
(4.25 to 5.5 V DC)
Rated input current
15.3 mA
On voltage/current
(for “a” contact)
3.5 V DC min./9 mA min.
Off voltage/current
(for “a” contact)
1.5 V DC max./ 2 mA max.
Common method
No internal common connection
Response time
1 ms max.
Figure 9.3 Connecting the Encoder Z-phase Input
15a
16a
F090103.VSD