2-8
IM 01F06A00-01E
2. INSTALLATION
Table 2.3(b) Installation of Flange Type Vortex Flowmeter
Horizontal Installation
Vertical Installation
Use the bolts and nuts supplied with the
flowmeter of the user.
The gaskets should be supplied by the user.
Flange type
Description
The inside diameter of the gasket must be
larger than the pipe inner diameter so that it
will not disturb the flow in the pipeline.
T020603.EPS
CAUTION
Flow Direction
Flow Direction
Nut
Nut
Bolt
Gasket
Gasket
Flange
Flange
Table 2.3(c) Installation of remote Type Converter
Remote type converter
Description
A signal cable (DYC) is used between the
remote type flowmeter and the converter.
The maximum signal cable length is 97.5ft
(30m).
The converter is mounted on a 2-inch (60.5mm outer dia.) stanchion or horizontal
pipe.
Do not mount the converter on a vertical pipe. It makes wiring and maintenance
difficult.
The converter mounting orientation can be changed as illustrated below.
T020604.EPS
CAUTION
Nut
Bracket
2-inch Pipe
U-Bolt
Horizontal Pipe Mounting
Stanchion Mounting