IM 01C25T01-01E
3-14
3. OPERATION
3.5.4
Unit for Displayed Temperature
When the instrument is shipped, the temperature units
are set to
C
(Centigrade). Follow the procedure below
to change this setting.
When this parameter is set, it also changes the tem-
perature unit for
Snsr temp
at
Process variables
and
Amp temp
at
Temp sensor
.
F0323.EPS
(ENTER)
EJX:YOKOGAWA
Temp Unit
degC
degC
degF
Kelvin
HELP
SEND
ESC
ENTER
Select
degF
(Fahrenheit), and
Press
ENTER (F4)
.
1. Device setup
4. Detailed setup
1. Sensors
3. Temp sensor
3. Temp Unit
Example: Change the unit for the temperature display from
degC to degF.
EJX:YOKOGAWA
Temp sensor
1 Snsr temp 23 degC
2 Amp temp 23 degC
3 Temp Unit degF
HELP
SEND
HOME
ENTER
2
1
Press
SEND (F2)
to send the data
to the transmitter, then check to
confirm that disappears.
(SEND)
SEND
3.5.5
Unit for Displayed Static Pressure
Follow the procedure to change the static pressure unit.
Changing this parameter also changes the unit for the
static pressure display.
F0324.EPS
(ENTER)
EJX:YOKOGAWA
SP Unit
mmH2O
kg/cm2
Pa
kPa
torr
HELP
SEND
ESC
ENTER
Select
kPa
and Press
ENTER (F4)
.
1. Device setup
4. Detailed setup
1. Sensors
2. SP sensor
3. SP Unit
Example: Change the static pressure unit from
mmH
2
O
to
kPa
.
EJX:YOKOGAWA
SP sensor
1 SP 0 mmH2O
2 SP % 0.0 %
3 SP Unit kPa
4 A/G Select
5 SP H/L Select High
HELP
SEND
HOME
ENTER
2
1
Press
SEND (F2)
to send the data
to the transmitter, then check to
confirm that disappears.
(SEND)
SEND