IM 01C25T01-01E
3-13
3. OPERATION
d. User Setting of Engineering Unit and Scale
Enter disp range
parameters allow the engineering
unit and scale to be displayed. At
Set Engr Unit
, the
following engineering units can be selected from a list.
Alternately, up to eight alphanumeric characters,
spaces or slashes (/) can be input on the keypad at
Modify Engr Unit
; only the first six are displayed on
the integral indicator.
Select the unit from the
Set Engr Unit
list.
FX0302.EPS
kPa
MPa
mbar
bar
psi
psia
mmH2O
mmHg
mmHgA
mmAq
mmWG
Torr
inH2O
inHg
inHgA
ftH2O
gf/cm2
kgf/cm2
kg/cm2G
kg/cm2A
atm
kg/h
t/h
m3/h
m3/min
l/h
l/min
kl/h
kl/min
Nl/h
Nl/min
Nm3/h
Nm3/min
ACFH
ACFM
SCFH
SCFM
GPH
GPM
m
mm
in
ft
kg/m3
g/cm3
Follow the procedure below to set your own unit.
Example: Set the engineering unit as
M/h
.
F0321.EPS
EJX:YOKOGAWA
Enter Engr Unit:
M/H
HELP
DEL
ABORT ENTER
1. Device setup
4. Detailed setup
4. Display condition
4. Engr disp range
7. Modify Engr Unit
Call up the
Modify Engr Unit
.
Set
M/H
, and press
ENTER (F4)
.
1
(ENTER)
EJX:YOKOGAWA
Enter space on the
characters to be
lowercase:
M/H
M/
HELP
DEL
ABORT ENTER
Enter a space instead of a character
to display the character in
lowercase, and press
ENTER (F4)
.
2
(ENTER)
×
2
Note that following symbols are not available:
# % & < > . * : + -
The integral indicator shows “-- -- -- -- -- --” when
these are entered.
Engr LRV
and
Engr URV
are used to set the lower
and upper range values for the engineering unit
display. When the insrument is shipped, these are set
as specified in the order.
F0322.EPS
Call up the
Engr LRV
Display.Set
–50
, and press
ENTER (F4)
.
EJX:YOKOGAWA
Engr LRV
0.0
-50
DEL
DEL
ESC
ENTER
EJX:YOKOGAWA
Engr disp range
1 Engr LRV -50
2 Engr URV 100
3 Engr exp
!
1
4 Engr Unit M
5 Engr point 1
HELP
SEND
HOME
ENTER
Press to select engr disp URV.
EJX:YOKOGAWA
Engr URV
100.0
50
DEL
DEL
ESC
ENTER
Set
50
, and press
ENTER (F4)
.
HELP
(ENTER)
‘– 5 0’
(ENTER)
‘5 0’
(SEND)
1. Device setup
4. Detailed setup
4. Display condition
4. Engr disp range
1. Engr LRV
and
2. Engr URV
Example: Set lower range value (LRV) to
–50
and upper
range value (URV) to
50
.
1
2
EJX:YOKOGAWA
Engr disp range
1 Engr LRV -50
2 Engr URV 50
3 Engr exp
!
1
4 Engr Unit M
5 Engr point 1
HELP
SEND
HOME
ENTER
4
3
Press
SEND (F2)
to send the data
to the transmitter, then check to
confirm that disappears.
(SEND)
SEND