IM 01C25T01-01E
3-9
3. OPERATION
3.4.4
Output Mode
The mode setting for the output signal and the integral
indicator can be performed independently.
The output mode for the output signal is set as speci-
fied in the order when the instrument is shipped.
Follow the procedure below to change the mode.
1
F0312.EPS
Call up the
Xfer fnctn
display.
EJX:YOKOGAWA
Xfer function
Linear
Linear
Sq root
DEL
SET
ESC
ENTER
[1] Select
Sq root
, and press
ENTER (F4)
.
[2] Press
SEND (F2)
to send the
data to the transmitter, then
check to confirm that
disappears.
(ENTER)
1. Device setup
3. Basic setup
5. Xfer fnctn
(SEND)
SEND
Example: To change the mode from
Linear
to
Sq root
.
3.4.5
Damping Time Constant Setup
The damping time constant is set as specified in the
order when the instrument is shipped. Follow the
procedure below to change the damping time constant.
The damping time constant for the amplifier assembly
can be set here. The damping time constant for the
entire transmitter is the sum of the values for the
amplifier assembly and the capsule assembly.
Any number from 0.00 to 100.00 can be set for the
damping time constant. Note that setting the quick
response parameter ON enables you to set the time
constant between 0.00 and 0.49 seconds.
1
Call up the
Quick resp
display to set the value to less
than 0.5 seconds.
EJX:YOKOGAWA
Quick resp
Off
Off
On
HELP
DEL
ESC
ENTER
Select
On
and press
ENTER (F4)
.
(ENTER)
2
EJX:YOKOGAWA
Signal condition
7 Low cut mode
8 H/L Swap Normal
9 Bi-dir mode Off
Quick resp On
T.Z. Cmp menu
HELP
SEND
HOME
ENTER
Press
SEND (F2)
to send the data
to the transmitter.
1. Device setup
4. Detailed setup
2. Signal condition
Quick resp
Example: To change from
2.0
seconds to
0.5
seconds
1
F0313.EPS
Call up the
Pres Damp
display.
EJX:YOKOGAWA
Pres Damp
2.00 sec
0.5
HELP
DEL
ESC
ENTER
Enter
0.5
and press
ENTER (F4)
.
(ENTER)
‘0 . 5’
2
EJX:YOKOGAWA
Basic Setup
3 Re-range
4 Device information
5 Xfer fncfn
6 Pres Damp 0.50 sec
7 Low cut 10.00 %
HELP
SEND
HOME
ENTER
Press
SEND (F2)
to send the data
to the transmitter.
1. Device setup
3. Basic setup
6. Pres Damp