IM 01C25T01-01E
3-12
3. OPERATION
3.5.3
Integral Indicator Scale Setup
The following five displays are available for integral
indicators: input pressure, % of range, user set scale,
input static pressure*
1
, and % of static pressure
range*
1
. A cycle of up to four displays can be shown
by assigning variables to the parameters at
Disp
select
.
T0303.EPS
Available displays
Input pressure
(PRES)
% of range
(PRES %)
User set scale
(ENGR. PRES)
Input static pressure
(SP)*
1
% of static pressure range
(SP %)*
1
Indicates values of input pressure
with the indication limits
99999 to
99999.
Indicates input pressure in
2.5 to
110% range depending on the
set range (
LRV
and
URV
).
Indicates values depending on the
engineering range (
Engr LRV
and
Engr URV
) with the unit (
Engr Unit
).
Indicates input static pressure with
the indication limits –99999 to 99999.
Reference pressure is factory-set in
absolute.
Indicates input static pressure in –10
to 110% range depending on the
set range (
SP LRV
and
SP URV
).
PRES 456
kPa
Description
and related parameters
PRES % 45.6 %
SP 4.000
MPa
SP %
52.6 %
Engr LRV 0.0
Engr URV 45.0
Engr exp
!
100
Engr Unit m3/min
Engr point 1
*
1: Available for differential pressure transmitter.
See (a.) through (d.) for the setting procedures.
a. Display Selection
At
Disp select
, select the variable that the parameter
Disp Out 1
will display on the integral indicator.
Example: Change from
PRES %
to
PRES
for the display.
F0320.EPS
(ENTER)
EJX:YOKOGAWA
Disp Out 1
PRES %
PRES %
ENGR. PRES
SP
SP %
HELP
SEND
ESC
ENTER
1. Device setup
4. Detailed setup
4. Display condition
1. Disp select
1. Disp Out 1
Press
SEND (F2)
to send the data
to the transmitter, then check to
confirm that disappears.
(SEND)
SEND
Call up the
Disp Out 1
display.
Select
PRES
, and press
ENTER
(F4)
.
EJX:YOKOGAWA
Disp select
1 Disp Out 1 PRES
2 Disp Out 2 Not Used
3 Disp Out 3 Not Used
4 Disp Out 4 Not Used
HELP
SEND
HOME
1
2
b. Cyclic Display
In addition to the display set at
Disp Out 1
, displays
can be set at
Disp Out 2
,
Disp Out 3
, and
Disp Out
4
for cyclic display in the order of the parameter
number.
c. Setting Static Pressure Scale
Static pressure can be displayed as a measured input or
as a percentage, independent from the 4-20 mA output
signal for measured pressure or differential pressure.
The
SP setup
parameters under
SP sensor
allow
the setting of the range, unit, and damping time
constant for the static pressure as well as the pressure
management range for PV.
Note that either the high or low pressure side of the
capsule can be selected to monitor the static pressure
by means of the
H/L Select
parameter under
SP
setup
.