IM 01C25T01-01E
3-10
3. OPERATION
3.4.6
Output Signal Low Cut Mode Setup
Low cut mode can be used to stabilize the output
signal near the zero point.
The low cut point can be set in a range from 0 to 20%,
the direct ratio corresponding to the output signal of 4
to 20 mA. (Hysteresis:
±
10% of the cut point)
Either
LINEAR
or
ZERO
can be selected as the low
cut mode. Unless otherwise specified, the cut mode is
set to LINEAR at the factory.
Note that when the output modes of the output signal
and the display are selected as
Sq root
and
Linear
accordingly, the low cut function is not available for
the display value.
(%)
50
(%)
50
0
50
(%)
50
(%)
Output
Output
For low cut in linear mode
Input
20
20
0
For low cut in zero mode
Input
F0314.EPS
Example: To set the low cut range to 20% and the cut mode
to ZERO in the
Sq root
output mode, proceed as
follows:
Figure 3.4.6 Low Cut Mode
F0315.EPS
EJX:YOKOGAWA
Low cut
10.00 %
10.00
HELP
DEL
ESC
ENTER
Call up
Low cut
, and set to 20%.
(ENTER)
(ENTER)
‘2 0’
EJX:YOKOGAWA
Low cut mode
Linear
Linear
Zero
HELP
SEND
ESC
ENTER
Select the
Low cut mode
, and set
to
Zero
.
EJX:YOKOGAWA
Basic Setup
4 Device information
5 Xfer fnctn Linear
6 Pres Damp 0.50 sec
7 Low cut 20.00 %
8 Low cut mode Zero
HELP
SEND
HOME
OK
Press
SEND (F2)
to send the date,
then check to confirm that
disappears.
(SEND)
1. Device setup
3. Basic setup
7. Low Cut and 8. Low cut mode
SEND
1
2
3
3.4.7 Impulse Line Connection Orientation
Setup
This function reverses the impulse line orientation.
Follow the procedure below to make this change.
F0316.EPS
(ENTER)
EJX:YOKOGAWA
H/L Swap
Normal
Normal
Reverse
HELP
SEND
ESC
ENTER
Press
SEND (F2)
to send the data
to the transmitter, then check to
confirm that disappears.
(SEND)
1. Device setup
3. Basic setup
9. H/L Swap
SEND
Call up the
H/L Swap
Display
Select
Reverse
, and press
ENTER
(F4)
.
EJX:YOKOGAWA
Basic setup
5 Xfer fnctn Linear
6 Pres Damp 0.50 sec
7 Low cut 20.00 %
8 Low cut mode Zero
9 H/L Swap Reverse
HELP
SEND
HOME
Example: Assign the high pressure impulse line connection
to the L side of the transmitter.
1
2