10. GENERAL SPECIFICATIONS
10. GENERAL SPECIFICATIONS
10.1
Standard Specifications
Refer to IM 01C22T02-01E for F
OUNDATION
Fieldbus communication type and IM 01C22T03-
00E for PROFIBUS PA communication type
marked with “
”.
Performance Specifications
See General Specifications sheet, GS 01C22K01-
00E.
Functional Specifications
Span & Range Limits
L
Capsule
M
Capsule
Differential
Pressure Span
inH
2
O
(/D1)
4 to 40
8 to 400
mbar
(/D3)
10 to 100
mmH
2
O
(/D4)
100 to 1000
20 to 1000 200 to 10000
kPa
1 to 10
2 to 100
H
Capsule
80 to 830 200 to 2100
0.05 to
5 kgf/cm
2
20 to 210
L
Capsule
M
Capsule
Measurement
Range
0.016 to 7.2
0.022 to 23.0
0.44 to 198
0.63 to 635
Water Equivalent
Flow l/min
Air Equivalent
Flow Nl/min
H
Capsule
0.07 to 33.0
2.0 to 910
T1001.EPS
Zero Adjustment Limits:
Zero can be fully elevated or suppressed, within
the Lower and Upper Range Limits of the capsule.
External Zero Adjustment “
”:
External zero is continuously adjustable with
0.01% incremental resolution of span. Span may
be adjusted locally using the digital indicator with
range switch.
Output “
”:
Two wire 4 to 20 mA DC output with digital
communications, linear or square root program-
mable. BRAIN or HART FSK protocol are superim-
posed on the 4 to 20 mA signal.
Failure Alarm:
Output status at CPU failure and hardware error;
Up-scale: 110%, 21.6 mA DC or more (standard)
Down-scale: –5%, 3.2 mA DC or less
–2.5%, 3.6 mA DC or less (Optional
code /F1)
Note: Applicable for Output signal code D and E
Damping Time Constant (1st order):
The sum of the amplifier and capsule damping
time constant must be used for the overall time
constant. Amp damping time constant is adjustable
from 0.2 to 64 seconds.
Time Constant (approx. sec)
0.4
0.3
0.3
L
M
H
T1002.EPS
Capsule (Silicone Oil)
Ambient Temperature Limits:
* Safety approval codes may affect limits.
–40 to 85
°
C (–40 to 185
°
F)
–30 to 80
°
C (–22 to 176
°
F) with LCD Display
Process Temperature Limits:
* Safety approval codes may affect limits.
–40 to 120
°
C (–40 to 248
°
F)
Working Pressure Limits (Silicone Oil)
2.7 kPa abs {20 mmHg abs} to maximum working
pressure. See ‘Model and Suffix Codes.’
Installation
Supply & Load Requirements “
”:
* Safety approvals can affect electrical requirements.
See Section 6.6, ‘Power Supply Voltage and Load
Resistance.’
Supply Voltage “
”:
10.5 to 42 V DC for general use and flameproof type
10.5 to 32 V DC for lightning protector (Optional code
/A)
10.5 to 30 V DC for intrinsically safe, Type n,
nonincendive, or non-sparking type
10.5 to 28 V DC for TIIS intrinsically safe type
EMC Conformity Standards:
,
EN61326, AS/NZS CISPR11
Communication Requirements “
”:
BRAIN
Communication Distance;
Up to 2 km (1.25 miles) when using CEV polyethyl-
ene-insulated PVC-sheathed cables.
Communication distance varies depending on type
of cable used.
Load Capacitance;
0.22
µ
F or less (see note)
Load Inductance;
3.3 mH or less (see note)
Input Impedance of communicating device;
10 k
Ω
or more at 2.4 kHz.
Note: For general-use and Flameproof type.
For Intrinsically safe type, please refer to
‘Optional Specifications.’