<7. Operation>
7-6
IM 01C25F01-01E
7.5.2 Activating Local Parameter Setting
Press the push button on the integral indicator to activate the Local Parameter Setting mode. The transmitter
will exit automatically from the Local Parameter Setting mode if no operation is carried out for 10 minutes.
7.5.3 Parameter Setting Review
Current setting value for the below parameters are shown sequentially by each press of the push button.
Tag number, Unit, LRV, URV, Damping,Output mode (linear/square root), Display out 1.
F0708.ai
push
push
push
push
push
Process
Measurement
Display
push
push
push
push
Process
Measurement
Display
*
*: [Software revision: 2.03] Up to 6 characters are shown in the bottom line. To review after the 7th character, turn the external
adjustment screw and press the push button six times or more.
[Software revision: 3.01 or later] The display automatically scrolls to show all the characters.
To configure each parameter value, turn the external adjustment screw on each parameter screen after
activating the Local Parameter Setting mode.
To cancel the Local Parameter Setting configuration, please refer to 7.5.11 Save or Cancel and 7.5.12 Abort
Configuration.