<2. Handling Cautions>
2-7
IM 01C25F01-01E
• Installation should be in accordance with
Canadian Electrical Code Part I and Local
Electrical Code.
• Dust-tight conduit seal must be used when
installed in Class II and III environments.
•
The instrument modification or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation and Yokogawa Corporation
of America is prohibited and will void
Canadian Standards Intrinsically safe and
nonincendive Certification.
F0204-1.ai
Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G
Pressure Transmitters
Safety Barrier
Supply
Hazardous Location
Nonhazardous Location
General
Purpose
Equipment
+
–
+
–
+
–
+
–
[Intrinsically Safe]
Group IIC, Zone 0
F0204-2.ai
Pressure Transmitters
Supply
Hazardous Location
Nonhazardous Location
+
–
+
–
Class I, II, Division 2,
Groups A, B, C, D, F, G
Class III, Division 1.
Not Use
Safety Barrier
[Nonincendive]
CSA Certified
Equipment
([nL] or
nonincendive)
Group IIC, Zone 2
b. CSA Explosionproof Type
Caution for CSA explosionproof type.
Note 1. EJX/EJA-E Series pressure transmitters
with optional code /CF1 are applicable for
use in hazardous locations:
• Certificate: 2014354
• Applicable Standard: C22.2 No.0,
C22.2 No.0.4, C22.2 No.0.5, C22.2 No.25,
C22.2 No.30, C22.2 No.94,
C22.2 No.61010-1, C22.2 No.60079-0,
C22.2 No.61010-2-030, C22.2 No.60079-1
• Explosion-proof for Class I, Groups B, C and
D.
• Dustignition-proof for Class II/III, Groups E, F
and G.
• Enclosure: Type 4X
• Temperature Code: T6...T4
• Ex d IIC T6...T4
• Enclosure: IP66/IP67
• Maximum Process Temperature: 120°C (T4),
100°C (T5), 85°C (T6)
• Ambient Temperature: –50* to 75°C (T4),
–50* to 80°C (T5), –50* to 75°C (T6)
* –15°C when /HE is specified.
• Supply Voltage: 42 V dc max.
32 V dc max. (F
OUNDATION
Fieldbus and
PROFIBUS PA type)
9 to 28 V dc, 27 mW (Low Power type)
• Output Signal: 4 to 20 mA dc
15 mA (F
OUNDATION
Fieldbus and
PROFIBUS PA type)
1 to 5 V (Low Power type)
Note 2. Wiring
• All wiring shall comply with Canadian
Electrical Code Part I and Local Electrical
Codes.
• In hazardous location, wiring shall be in
conduit as shown in the figure.
• WARNING:
A SEAL SHALL BE INSTALLED WITHIN
50cm OF THE ENCLOSURE.
UN SCELLEMENT DOIT ÊTRE INSTALLÉ À
MOINS DE 50cm DU BOÎTIER.
• WARNING:
WHEN INSTALLED IN CL.I, DIV 2, SEAL
NOT REQUIRED.
UNE FOIS INSTALLÉ DANS CL I, DIV 2,
AUCUN JOINT N'EST REQUIS.
Non-hazardous
Location
Equipment
42 V DC Max.
4 to 20 mA DC
Signal
Non-Hazardous
Locations
Hazardous Locations Division 1
50 cm Max.
Sealing Fitting
Conduit
Transmitter
F0205-1.ai
Non-Hazardous
Locations
Hazardous Locations Division 2
Non-hazardous
Location
Equipment
42 V DC Max.
4 to 20 mA DC
Signal
Sealing Fitting
Transmitter
F0205-2.ai