<7. OPERATION VIA BRAIN TERMINAL (BT200)>
7-3
IM 01E30D01-01EN
7.2 AXR Operation Using a
BT200
This section describes procedures for setting
parameters using a BRAIN Terminal (BT200).
For more details regarding AXR functions, read
Chapter 6 and for more details regarding BT200
operation methods, read the BT200 User’s Manual
(IM 01C00A11-01E).
7.2.1 BT200 Connection
Connection to a 4 to 20 mA DC signal line
The communication signal is superimposed onto
the 4 to 20 mA DC analog signals to be transmitted.
AXR terminals
BT200
BT200
Relaying
terminals
4 to 20 mA
DC signal
transmission
line
F0707.ai
BT200
BT200
Control room
Receiving
instrument
load
resistance:
250 to 600Ω
Terminal
Board
Distributor
SUPPLY
DO
Figure 7.2
Connecting the BT200
IMPORTANT
Communication signal is superimposed on
analog output signal. It is recommended to set
a low-pass filter (approximately 0.1s) to the
receiver in order to reduce the output effect
from communication signal. Before online-
communication, confirm that communication
signal does not give effect on the upper system.
IMPORTANT
Restrictions exist with regard to the distance
over which communication is possible. When
simultaneous output of current and pulse output
or pulse output are used, no communication is
possible depending on the wiring. Read Section
4.6 and Chapter 12 in detail.
IMPORTANT
If the power of flowmeter is turned off within 30
seconds after parameters have been set, these
settings will be canceled. Accordingly, please
keep the power on for at least 30 seconds after
setting parameters.
IMPORTANT
After approximately 5 minutes of inactivity, the
Auto Power-Off function will operate to turn your
BT200 off.
WARNING
Be sure to set parameters as “Protect” on the
write protect function after finish of parameter
setting work.
Read Chapter 6 Menu P and Subsection 11.3.2,
how to use the write protect function in detail.
NOTE
In case of BT200, the parameters are displayed
in English only.
Even if the language with the exception of
English is selected at
B10/H30: Language
,
the parameters are displayed in English upon
BT200.