IM 01E20F02-01E
8-7
8. PARAMETER LISTS
T0802-4.EPS
Write
Mode
Explanation
Factory
Default
Relative
Index
Parameter Name
Index
Indicate the value of switch 2, which switches ON and OFF
depending on the digital value of the target input parameter
selected in SWITCH_2_TARGET.
This parameter selects the input channel used to
LIMSW_2_VALUE_D.
1: Adhesion Alarm
2: Adhesion Warning
When "2:Lock" is selected, signal lock function becomes active
and output is fixed to 0%.
1: Unlock
2: Lock
Sets the cycle for the display unit's display-response speed.
Settings should be made in accordance with the measurement
environment, e.g. Set the longer display cycle when using the
equipment in low temperature environment.
1: 200ms 2: 400ms 3: 1s 4: 2s 5: 4s 6: 8s
Sets the rate limit value. Valid range is 0 to 10%.
Sets the dead time for late limit function, if 0 is set then the rate
limit function becomes inactive. Valid range is 0 to 15 s.
Set 2: Yes if flow is pulsing. Valid range is 1: No 2: Yes.
This parameter is used to indicate whether or not the internal
frequency is to be synchronized with that of power supply
frequency. Valid range is 1: No 2: Yes
Sets the power frequency. Valid range is 47.00 to 63.00 Hz.
Display the software revision number. Set in ASCII code 8
characters.
This parameter masks Alarm/Warning. By setting "0" to each bit,
corresponding Alarm/Warning are cleared. When masked the
corresponding bit of DEVICE_STATUS becomes OFF and no
alarm is displayed on LCD, and also becomes out of scope of
Primary value status, ED_ERROR setting. Valid range is
0x00000000 to 0x007f003f
This parameter displays the operation time, e.g. "1D23:45"
indicates an operation time of 1 day, 23 hours and 45 minutes.
Valid range is 0D 00:00 to 99999D 23:59
65 2065
This parameter selects the input channel used to
LIMSW_1_VALUE_D.
1: Adhesion Alarm
2: Adhesion Warning
64
2064 SWITCH_1_TARGET 1: Adhesion Alarm
O/S
66 2066
SWITCH_2_TARGET
O/S
67 2067
SIGNAL_LOCK
1:
Unlock
Auto
68 2068
DISPLAY_CYCLE
2:
400ms
Auto
69 2069
RATE_LIMIT
5
O/S
70 2070
RATE_LIMIT_
0
O/S
71 2071
PULSING_FLOW
1:
No
O/S
72 2072
POWER_SYNCH
2:
Yes
O/S
75 2075
ALARM_PERFORM 0x00010033
O/S
76
2076 OPERATION_TIME
0D 00: 00
Display the most-recent alarm. Valid range is
0: space, 1: 10:
P fault, 2: 11: EEPROM Fault,
3: 12: A/D (H) Fault, 4: 13: A/D (L) Fault, 5: 14: A/D (Z) Fault,
6: 15: Coil Open, 7: 16: EEPROM Dflt, 8: 18: Power Off,
9: 19: Inst Pwr Fail, 10: 28: WDT, 11: 30: Sig Overflow,
12: 31: Empty Pipe, 13: 33: Adhesion Alm, 14: 34: Insu-Brk Alm
77 2077
ALM_RECORD1
0
Display the operation time at which the alarm indicated by
Alm_record1 was occurred. For example, "1D23:45" indicates
that an alarm was triggered at the operation time of 1 day, 23
hours and 45 minutes. Valid range is 0D 00:00 to 99999D 23:59
78
2078
0D 00: 00
Display the second most-recent alarm. Valid range is the same
as ALM_RECORD_TIME1
79 2079
ALM_RECORD2
0
This parameter is used to display the operation time at which the
alarm indicated by Alm_Record2 occurred.
80
2080
0D 00: 00
Display the third most-recent alarm. Valid range is Valid range is
the same as ALM_RECORD_TIME1
81 2081
ALM_RECORD3
0
This parameter is used to display the operation time at which the
alarm indicated by Alm_Record3 occurred.
82
2082
0D 00: 00
Display the fourth most-recent alarm. Valid range is Valid range
is the same as ALM_RECORD_TIME1
83 2083
ALM_RECORD4
0
This parameter is used to display the operation time at which the
alarm indicated by Alm_Record4 occurred.
84
2084
0D 00: 00
73 2073
50
O/S
74 2074
SOFTWARE_
REV_NO
POWER_
FREQUENCY
SWITCH_2_
VALUE_D
ALM_RECORD_
TIME1
ALM_RECORD_
TIME2
2: Adhesion
Warning
ALM_RECORD_
TIME3
ALM_RECORD_
TIME4
DEAD_TIME