IM 01E20F02-01E
5-5
5. EXPLANATION OF BASIC ITEMS
OUT:
This parameter contains the current measurement value
from Transducer Block or configuration adjusted
engineering unit and the belonging state in AUTO
MODE. OUT contains the value and status set by an
operator in MAN MODE.
Quality
Sub-status
Limit
Alarm
Non-specific
Normal
Active Block Alarm
Block Alarm is Active
Active Advisory Alarm
Advisory Alarm is Active
Active Critical Alarm
Critical Alarm is Active
Unack. Block Alarm
Block Alarm is Unacknowledged
Unack. Advisory Alarm
Advisory Alarm is Active
Good(NC)
Unack. Critical Alarm
0:Not Limited
1:Low Limited
2:High Limited
3:Constant
0:Not Limited
1:Low Limited
2:High Limited
3:Constant
Critical Alarm is Active
Uncertain
Engineering Unit Range
Violation
--
--
Out of sensor operating range
Out of range of min. span and max. span
No-specific
FB board EEPROM failure
TB is O/S
BLOCK_ERR is O/S etc.
Device Failure
EEPROM failure
Internal communication error
Sensor Failure
CPU board failure
Bad
Out of Service
--
RS, AI are O/S
T0503.eps
XD_SCALE:
Scale of input from the transducer block. The maxi-
mum flow rate range on an order sheet is set. "0" (0%),
"10.000"(100%), and "m/s" for the unit are factory-set
unless specified in the order. Changing the unit (can be
set only in flow rate) also causes the unit within the
transducer block to be automatically changed.(The unit
is automatically changed according to the unit selected
in AI. Units which can be set by XD_SCALE are
shown in Table 5.4.1.