YMGI • Your Modern Green Idea
YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World!
44
PROTECTION AND ERROR CODES
ERROR OR PROTECTION CODE INDICATION
When the Indoor unit is controlled by wired controller, error or protection codes are as follows:
NO.
Meaning
Code Indicated
on display
1
Compressor high pressure protection unit stop
E1
2
Indoor unit anti-freezing protection
E2
3
Low-pressure protection unit stop
E3
4
Air exhaust protection unit stop
E4
5
Over current protection unit stop
E5
6
Communication malfunction unit stop
E6
7
Unit modes conflict
E3
8
Jumper malfunction
E3
9
Defrosting /Heating oil return
Defrost
10
Compressor overload protection unit stop
E5
11
System Unit malfunction
F2
12
IPM modular protection unit stop
E5
13
PFC protection unit stop
E5
14
Compressor malfunction
E9
15
Water spill protection
E9
16
Indoor ambient temp. sensor malfunction
F0
17
Indoor pipe temp. sensor malfunction
F1
18
Outdoor ambient temp. sensor malfunction
F3
19
Outdoor pipe temp. sensor malfunction
F2
20
Outdoor air exhaust temp. sensor malfunction
F4
21
E2 PROM Error
E3
22
Wire control ambient temp. sensor malfunction
F5