YMGI • Your Modern Green Idea
YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World!
15
Specification Sheet
Items
Unit / Conditions
WMMS-12EC-V2B(59)2
WMMS-18EC-V2B(59)2
WMMS-24EC-V2B(59)2
Power Supply
Voltage/Ph/Hz
208-230/1/60
208-230/1/60
208-230/1/60
Allowed Voltage Range
187-253V
187-253V
187-253V
Cooling Capacity (Btu/h)
High/Standard/Low
13900/12000/5200
20800/17200/6200
26500/22800/9600
Heating Capacity (Btu/h)
ID 70/60, OD 47/43F
13000
18100
27400
ID 70/60, OD 17/15F
11600
16200
23800
ID 70/60, OD 17/5F
9000
13100
20600
SEER
Btu/h.W
16
16
16
HSPF
Btu/h.W
8.2
8.2
8.2
Dehumidifying Capacity
Pints/Hr.
2.96
3.8
5.28
Air Flow (CFM)
High/Medium/Low
353/312/245
353/312/245
694/522/366
Air-throw (Ft.)
Horizontal Installation
25-18 Upon Mounting
Height/Speed/Temp.
External Static Pressure
Water In.
0
0
0
Sound Level
Pressure dB(A) (H/M/L)
39/37/35
39/37/35
45/43/41
Power dB(A) (H/M/L)
49/47/45
49/47/45
55/53/51
Fan Motor
Model
FN11T-2
FN11T-2
FN35B-1
Shaft
Single
Single
Single
Speed (RMP, H/M/L)
700/600/515
700/600/515
570/520/280
Output (W)
11
11
50
Input (W)
50
50
165
Capacitor (uF)
1
1
3
Fan Wheel
Type-Piece
Centrifugal-1
Centrifugal-1
Centrifugal-1
Diameter x Height (In.)
11.1 x 5.8
11.1 x 5.8
17.7 x 4.4
Swing/Step Motor
Model
MP35CB
MP35CB
MP35CB
Piece
2
2
2
Output (W)
2
2
2
Input Power of
Elec. Heater
Type-W
NA
NA
NA
Electrical Protection Fuse
PCB / Transformer
T3.15A 250V / 0.2A
Evaporator Coil
Type
Aluminum Fin/Inner Grooved Copper Tube
Color
Blue
Copper Line Connections
Sealed by Dry Nitrogen
Yes
Yes
Yes
Flare/Nut- Gas
1/4" + 3/8"
1/4" + 1/2"
1/4" + 5/8"
Drain Hose Connection
OD (In.)
1.22
1.22
1.22
Condensate Pump
Installed-Lift (In.)
Yes-25
Yes-25
Yes-25
Refrigerant Environmental
Friendly
R410A
Yes
Yes
Yes
Filter
Type-Feature
Standard-Washable
Standard-Washable
Standard-Washable
Size W x H (In.) / Qty.
13.56 x 13.13 / 1
13.56 x 13.13 / 1
21.38 x 21.34 / 1
Clean Coil Surface
Anti-Mildew Function
Yes
Yes
Yes
Pre-heating Function
Anti-Cold Blowing
Yes
Yes
Yes
Memory of
Previous Set-ups
Power is Lost/Resumed
Yes
Yes
Yes
Auto-Restart Function
If Power is Resumed
Yes
Unit Dimensions
Net L x W x H (In.)
22.4 x 22.4 x 9.1
22.4 x 22.4 x 9.1
33.1 x 33.1 x 9.4
Package L x W x H (In.)
33.4 x 28.7 x 12.2
33.4 x 28.7 x 12.2
37.8 x 37.8 x 12.2
Unit Weight
Net (LBs)
39.7
39.7
66
Packaged (LBs)
50.7
50.7
84
Face Panel Dimensions
Net L x W x H (In.)
25.6 x 25.6 x 2
25.6 x 25.6 x 2
37.4 x 37.4 x 2.4
Package L x W x H (In.)
28.7 x 26.4 x 4
28.7 x 26.4 x 4
40.9 x 40.4 x 4.5
Face Panel Weight
Net (LBs)
5.5
5.5
14
Packaged (LBs)
8.1
8.1
22
Notes:
1. Performance rated for matched system at standard conditions-cooling ID 80/67°F, OD 95°F; heating ID 70/60°F, OD 47/43°F,
25 ft. copper lines and IDU 7ft. above ODU. Unit performance varies when weather changes from the standard one.
2. Select equipment capacity sizes per space load calculation schedule and cooling & heating hours. Not to over size or under
size equipment.
3. Watch unit operation during extreme weather conditions in summer and winter. Wind baffle helps system cooling & heating
performance in low ambient temperature ranges.
4. Heating capacities up to 85% @ 17°F ambient temperature, up to 60% @ -4°F varying upon geographic location and actual
installation.