YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World!
48
LED Display
Key:
★ : LIGHT
○ : FLASHING LIGHT
X : OFF
Flash cycle is 1 second
Error Code
Sleep
Timer
Running
Issue
Cause may be one of the following:
1
2
3
0
Normal Operation
1
○
★
★
Outdoor coil temperature
sensor failure
Outdoor temperature sensor loose
Outdoor temperature sensor failure
Indoor control board failure
2
Compressor exhaust
temperature sensor issue
Compressor exhaust temperature sensor is
loose
Compressor exhaust temperature sensor
failure
Outdoor control board failure
5
★
○
X
IPM module protection
IPM board failure
Outdoor fan is broken
Outdoor fan motor failure
Outdoor fan is blocked
Dirty condenser
Outdoor unit has been installed incorrectly
6
X
○
X
AC voltage high or low
protection
Supplied voltage is higher or lower than
normal
Internal supplied voltage of the unit is higher
or lower than normal
7
★
★
X
Communication failure
between Indoor unit and
Outdoor unit
Communication cable is loose
Communication cable failure
Connection between filter board and outdoor
control board is incorrect or loose
Connection between the filter board and
terminal is incorrect or loose
PFC board failure
Power board failure
Outdoor control board failure
8
Current overload
protection
Fan motor is running abnormally
Dirty condenser and evaporator
Air inlet and/or outlet is abnormal
9
Maximum current
protection
Outdoor control board has a short circuit
Drive board has short circuit
Another component has a short circuit
10
★
X
X
Communication issue
between Outdoor unit and
driver
Connection wires connection loose
Outdoor board or drive board failure
11
○
X
X
Outdoor EEPROM issue
EEPROM chip is loose
EEPROM chip is installed backwards
EEPROM chip failure