YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World!
45
Key:
★ : LIGHT
○ : FLASHING LIGHT
X : OFF
Flash cycle is 1 second
Error Code
Running
Timer
Sleep
Power
Issue
Cause may be one of the following:
1
2
3
4
0
Normal Operation
1
X
○
X
X
Outdoor coil temperature
sensor failure
Outdoor temperature sensor
connection is loose
Outdoor temperature sensor failure
Indoor control board failure
2
X
○
★
X
Compressor exhaust
temperature sensor issue
Compressor exhaust temperature
sensor connection is loose
Compressor exhaust temperature
sensor failure
Outdoor control board failure
5
★
○
X
X
IPM module protection
IPM board failure
Outdoor unit fan is broken
Outdoor unit fan motor failure
Outdoor unit fan motor is blocked
Condenser is dirty
Outdoor unit not installed properly
6
★
○
X
★
AC voltage out of range
protection
Supplied voltage is higher or lower
than normal
Indoor unit supply voltage is higher
or lower than normal
7
★
○
★
X
Communication failure
between Indoor Unit and
Outdoor Unit
Communication cable connection is
loose
Communication cable failure
Connection between the filter board
and the outdoor control board is
incorrect or loose
Connection between the filter board
and the terminal is incorrect or loose
Indoor control board failure
PFC board failure
Power board failure
Outdoor control board failure
8
★
○
★
★
Current overload
protection
Fan motor is running abnormally
Condenser and evaporator are dirty
Air inlet and/or outlet is abnormal
9
X
X
○
X
Maximum current
protection
Outdoor control board has a short
circuit
Drive board has a short circuit
Other component has a short circuit
10
X
X
○
★
Communication issue
between Outdoor unit and
driver
Connection wires connection loose
Outdoor board or drive board failure