YMGI
•
Your Modern Green Idea
69
Error
Code
Content
Error
Code
Content
P2
Voltage protection of driving board power of compressor
bF
Malfunction of outlet tube temperature sensor of
condenser
P3
Reset protection of driving module of compressor
bJ
High-pressure sensor and low-pressure sensor are
connected reversely
P4
Drive PFC protection of compressor
bP
Malfunction of temperature sensor of oil-return 2
P5
Over-current protection of inverter compressor
bU
Malfunction of temperature sensor of oil return 3
P6
Drive IPM module protection of compressor
bb
Malfunction of temperature sensor of oil return 4
P7
Malfunction of drive temperature sensor of compressor
H0
Malfunction of driving board of fan
P8
Drive IPM high temperature protection of compressor
H1
Driving board of fan operates abnormally
P9
Desynchronizing protection of inverter compressor
H2
Voltage protection of driving board power of fan
PA
Malfunction of drive storage chip of compressor
H3
Reset protection of driving module of fan
PH
High-
voltage protection of compressor’s drive DC bus bar
H4
Drive PFC protection of fan
PC
Malfunction of current detection circuit drive of compressor
H5
Over-current protection of inverter fan
PL
Low voltage protection for DC bus bar of drive of
compressor
H6
Drive IPM module protection of fan
PE
Phase-lacking of inverter compressor
H7
Malfunction of drive temperature sensor of fan
PF
Malfunction of charging loop of driven of compressor
H8
Drive IPM high temperature protection of fan
PJ
Failure startup of inverter compressor
H9
Desynchronizing protection of inverter fan
PP
AC current protection of inverter compressor
HA
Malfunction of drive storage chip of inverter outdoor fan
PU
AC input voltage of drive of inverter compressor
HH
High-
voltage protection of fan’s drive DC bus bar
F0
Main board of ODU is poor
HC
Malfunction of current detection circuit of fan drive
F1
Malfunction of high-pressure sensor
HL
Low voltage protection of bus bar of fan drive
F3
Malfunction of low-pressure sensor
HE
Phase-lacking of inverter fan
F5
Malfunction of discharge temperature sensor of
compressor 1
HF
Malfunction of charging loop of fan drive
F6
Malfunction of exit-tube temperature sensor
HJ
Failure startup of inverter fan
F7
Malfunction of humidity sensor
HP
AC current protection of inverter fan
F8
Malfunction of water temperature sensor
HU
AC input voltage of drive of inverter fan
F9
Malfunction of jumper cap
HJ
Failure startup of inverter fan
FA
Web address of IDU is abnormal
HP
AC current protection of inverter fan
FH
Current sensor of compressor 1 is abnormal
HU
AC input voltage of drive of inverter fan