14
Combinations of Indoor and Outdoor Units
Model
Max number of
connectable IDU
(unit)
ODU Model
Max number of
connectable IDU
(unit)
VRFO-
72
VP-U2C(55)5
12
VRFO-
240
VP-U2C(55)5
41
VRFO-
96
VP-U2C(55)5
16
VRFO-
264
VP-U2C(55)5
45
VRFO-
120
VP-U2C(55)5
20
VRFO-
288
VP-U2C(55)5
49
VRFO-
144
VP-U2C(55)5
25
VRFO-
312
VP-U2C(55)5
53
VRFO-
168
VP-U2C(55)5
29
VRFO-
336
VP-U2C(55)5
58
VRFO-
192
VP-U2C(55)5
33
VRFO-
360
VP-U2C(55)5
61
VRFO-
216
VP-U2C(55)5
37
The total capacity of indoor units should be within 50%~135% of that of outdoor units.
Fig.2
Fig.2 is the combination view of the ODU of Modular DC Inverter Multi VRF System and the IDU of Multi VRF System.
IDU can be cassette type, one-way cassette type, wall-mounted type, duct type, etc. When any one IDU receives
operation signal, ODU will start to work according to the capacity; when all IDUs stop, ODU will also stop.
The Range of Production Working Temperature
Cooling
Ambient temperature: -5ºC(23ºF)~52ºC(125.6ºF)
Heating
Ambient temperature: -20ºC (-4ºF)~24ºC (75.2ºF)
Running this system outside of the working temperature range may damage the unit and will invalidate the
warranty.