9. Specifications
113
Standard Wiring
Shielded
Shielded twisted-pair cable
: Only basic insulation (Protective class 1, overvoltage categoly II) is provided for the
control circuit terminals. Additional insulation may be necessary in the end product
to conform to CE requirements.
P
Short-circuit bar
*1
MCCB
For single-phase,
use R/L1 and S/L2.
R
S
T
R/L1
S/L2
T/L3
U/T1
IM
V/T2
W/T3
S1
S2
S3
S4
S5
SC
MA
MB
MC
U
X
−
+1
+2
Multi-function
*2
output
250 VAC 1 A or less
30 VDC 1 A or less
RUNNING
Multi-function inputs
FORWARD
RUN/STOP
REVERSE
RUN/STOP
FAULT RESET
EXTERNAL FAULT
(NO Contact)
MULTI-STEP
SPEED REF.1
Frequency Ref.
2 k
Ω
P
P
Shielded Connection
Terminal
FS
FR
FC
Frequency Setting
Potentiometer
Frequency Setting Power Supply
(+12 V 20 mA)
Speed Frequency Reference
0 to +10 V (20 k
Ω
) or
4 to 20 mA/0 to 20 mA (250
Ω
)
0 V
Digital Operator
Frequency
Setting
Volume
MIN
MAX
DC Reactor
(Option)
AM
AC
P
FM
Output Frequency
Analog Monitor
Output
0 to +10 VDC
(2 mA)
*1. Shorting bar must be removed when connecting DC reactor.
*2. Minimum permissible load: 5 VDC, 10 mA (as reference value)