6. Programming Features
49
Selecting RUN/STOP Commands
Refer to
Switching LOCAL/REMOTE Mode
(page 48) to select either
the LOCAL mode or REMOTE mode.
The operation method (RUN/STOP commands, FWD/REV RUN com-
mands) can be selected using the following method.
LOCAL Mode
When Lo (local mode) is selected for Digital Operator
ON
mode, or when the LOCAL/REMOTE switching function is set and the
input terminals are turned ON, run operation is enabled by the
or
on the Digital Operator, and FWD/REV is enabled by the
ON mode (using
or
key).
is not effective when local/remote switching function is
selected for multi-function input selection.
REMOTE Mode
1. Select remote mode.
There are following two methods to select remote mode.
• Select rE (remote mode) for the
selection.
• When the local/remote switching function is selected for the
multi-function input selection, turn OFF the input terminal to
select remote mode.
2. Select the operation method by setting constant n02.
n02 =0: Enables the Digital Operator (same with local mode).
=1: Enables the multi-function input terminal (see fig. below).
=2: Enables communications (refer to page 83) (When option
card is installed).
• Example when using the multi-function input terminal as opera-
tion reference (two-wire sequence)
For an example of three-wire sequence, refer to page 70.
FWD RUN/STOP
REV RUN/STOP
n02: 1 (Initial setting: 0)
n36: 2