4. Wiring
31
Wiring the Control Circuits
Only basic insulation is provided for the control circuit terminals.
Additional insulation may be necessary in the end product.
• Control Circuit Terminals
Pass the cable through wiring hole to connect it. Always mount the
cover in its original position.
SW7 can be changed according to sequence input signal (S1 to S5)
polarity.
0 V common: NPN side (Initial setting)
+24 V common: PNP side
Refer to page 115 for SW7.
Refer to page 75 for SW8.
Insert the wire into the lower part of the terminal block and connect
it tightly with a screwdriver.
The wire sheath strip length must be 5.5 mm.
0.4 mm max
2.5 mm max
Wiring the Control Circuit Terminals
Screwdriver Blade Width
5.5 mm